How to bring real equipment onto a BMS over BACnet: chillers, rooftop units, boilers, VRF controllers, drives, pumps, valves and routers. Each guide covers what to switch on, the factory addresses and instances, the points a BMS uses, the rule that bites in the field — tested against a simulated device — and a free BACManager workspace to download.
13 devices · made from the makers' own manuals, PICS and EDE lists
Daikin MicroTech III chiller on BACnet MS/TP or IP: module, keypad setup, key points list, priority 8 writes, why setpoints are ignored. Free workspace.
Trane Symbio 700 rooftop on BACnet MS/TP or IP: rotary address, app setup, J17 wiring, key points, the priority 14 rule. Symbio 800 notes. Free workspace.
AAON VCCX2 on BACnet MS/TP: LCD setup, the BACnet port vs the 485 loop, key points, overrides released by 65535, the damper trap. Free workspace.
Lennox CORE on BACnet MS/TP or IP: setup wizard, defaults, key points, and the 5-minute rule that drops a unit into backup mode. Free workspace.
Lochinvar Crest boiler on BACnet MS/TP: MTR-01 DIP switches, device instance, Configuration bits, the BAS timer, setpoint in %. Free workspace.
Daikin iTM BACnet Server Gateway: activation, the CSV, device instances 53PGGG, network 100, Occupancy Mode as on/off, EEPROM limits. Free workspace.
Mitsubishi AE-200 / EW-50 on BACnet/IP: licence, Setting Tool, LAN2, Device No. 3, instance numbers per group, 200 ms per property. Free workspace.
ABB ACH580 drive on BACnet MS/TP: group 58 setup, device ID 4194303, BV10/AV16 control, why it trips on 6681 EFB comm loss. Free workspace.
Altivar Process ATV600 on BACnet MS/TP with VW3A3725: address and instance 0, the 1 s fieldbus timeout, CnF, control channel. Free workspace.
Grundfos MAGNA3 on BACnet with CIM 300 or CIM 500: switches, instance 227000 + MAC, bus control, setpoint scaling, the watchdog. Free workspace.
Wilo-Stratos MAXO on BACnet with a CIF-Module: MS/TP or IP, no ReadPropertyMultiple on MS/TP, values on change only, bus command timer. Free workspace.
Belimo Energy Valve 4 on BACnet: protocol None from the factory, setpoint source Analog, the bus watchdog, units and the points list. Free workspace.
Contemporary Controls BASrouter: MS/TP to BACnet/IP, factory IP, network numbers, instance 0, bias jumpers, router vs gateway. Free workspace.
The option card, the licence or the menu, and the factory MAC, baud rate and device instance — which is often the same on every unit.
Object types, instances and names as the maker gives them, with what to write and what only to read.
Watchdogs that expect a write again, setpoints that only count on a change, routers, request intervals — shown on a simulated device in BACManager, with and without the fix.
Every guide names the manuals, PICS and EDE lists it was made from. The makers' names and product names are trademarks of their owners; BACManager is not affiliated with any of them.
Download the free trial, discover the device and open its workspace — every point by name. No credit card.
Windows 10/11 · $149 one-time