Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: ModbusManager ↗
// accuenergy · acuvim ii / iir · power meter

Acuvim II
BACnet Points List & Setup

How to read an Accuenergy Acuvim II power meter over BACnet: Protocol 1 to BACNET on the meter's own RS-485 (it ships as Modbus), the device ID in S52, the 71 Analog Inputs from Frequency (AI1) to current THD (AI71) — and why the old AXM-BMS module serves a different list. Read-only, so a BMS polls it. With a free BACManager workspace.

Download free trial Free Acuvim II workspace

Sources: Accuenergy Acuvim II Series Power Meter User Manual V3.2.17, the BACnet user's manual 1040E2102 V2.0.1 and BTL listing BTL-30936

// before you start

Three ways to BACnet, two object lists

🔌

Native MS/TP

Current meters speak BACnet MS/TP on their own RS-485 terminals (A = Data+, B = Data−, S = shield). This is the path in the main user manual and the BTL listing, and it serves AI1–AI71.

🌐

BACnet/IP

Through the AXM-WEB2 module (older units: AXM-BIP), set up in the module's web page: BACnet enabled, port 47808, device instance, network number, optional BBMD registration. Same AI1–AI71 list.

⚠

Older AXM-BMS module

The add-on MS/TP module of older meters has its own list: 56 Analog Values AV0–AV55, numbered from 0, with short names like Ua_rms. A workspace made for AI1–AI71 reads nothing there — look at the object list first.

// setup

Settings → SYS, five pages

On the meter: press H and V/A together for about a second, choose Setting, enter the password, then SYS. Each page is accepted with V/A.

PageFactorySet to
S01 Address—The meter's MS/TP MAC on the trunk
S02 Baud rate19200The trunk's rate. BACnet MS/TP: 9600, 19200, 38400, 57600, 76800 or 115200
S38 Protocol 1ModbusBACNET — nothing answers on BACnet before this
S51 MS/TP Max Info Frames101–255; usually leave
S52 MS/TP BACnet IDnot givenA device instance unique in the building, 0–4194302

The manual gives no factory device ID and no Max Master setting for the native port; check S52 on every meter rather than assuming. The AXM-BMS module is set up elsewhere — S34 Protocol 2 = BACNET, then the NET menu (MAC 0, 9600 baud, Max Info Frames 1 from the factory) and a module reset.

// the rules that bite

Modbus first, read-only, a silent minute

S38

It ships as Modbus

Protocol 1 leaves the factory as Modbus. A meter wired onto an MS/TP trunk stays invisible to Who-Is until S38 says BACNET — and a Modbus slave on an MS/TP trunk does nothing for the token either.

R

Read-only

The BTL listing gives the meter the Smart Sensor profile: ReadProperty, ReadPropertyMultiple and discovery — no WriteProperty and no COV. The BMS has to poll; energy is cleared on the meter (S25) or over Modbus, not over BACnet.

60 s

The DIN-rail model's first minute

From firmware 6.20 the Acuvim IIV3-M (DIN rail, no display) keeps channel 1 on Modbus at 9600 for 60 seconds after every power-up, as a way back in if it was set wrong. BACnet starts after that minute.

// points list

The Acuvim II points a BMS uses

All Analog Inputs, floating point, read only, with the unit in the object. Native MS/TP and BACnet/IP (AXM-WEB2 / AXM-BIP).

BACManager BACnet tab: device Acuvim II MDB-1, instance 41001, with its Analog Inputs listed by name and polled: Frequency, Phase A Voltage, Phase A Current, Total Active Power, Total Power Factor, Import Active Energy and the others
The meter's objects by name in BACManager (simulated meter built from Accuenergy's object table)
ObjectObject nameUnit
AI1FrequencyHz
AI2–4 / AI5Phase A/B/C Voltage / Average Phase VoltageV
AI6–8 / AI9Line Voltage AB/BC/CA / Average Line VoltageV
AI10–12 / AI13 / AI14Phase A/B/C Current / Average Current / Neutral CurrentA
AI15–17 / AI18Phase A/B/C Active Power / Total Active PowerkW
AI19–21 / AI22Phase A/B/C Reactive Power / Total Reactive Powerkvar
AI23–25 / AI26Phase A/B/C Apparent Power / Total Apparent PowerkVA
AI27–29 / AI30Phase A/B/C Power Factor / Total Power Factor—
AI31 / AI32Voltage / Current Unbalance Factor%
AI34–36 / AI37–39Active / Reactive / Apparent Power Demand, Phase A/B/C Current DemandkW, kvar, kVA, A
AI40 / AI41Import / Export Active EnergykWh
AI42 / AI43Import / Export Reactive Energykvarh
AI44 / AI45, AI46 / AI47, AI48Energy Total / Net, Reactive Energy Total / Net, Apparent EnergykWh, kvarh, kVAh
AI49–63per-phase import/export active and reactive energy, apparent energykWh, kvarh, kVAh
AI64–66 / AI67Phase A/B/C Voltage THD / Average Voltage THD%
AI68–70 / AI71Phase A/B/C Current THD / Average Current THD%

AI33 Load Type is in the list without its coding. The power factor sign follows the meter's VAR/PF convention (IEC or IEEE, set on the meter). On the AXM-BMS module the same quantities are AV0–AV55 in the same order, starting with AV0 Freq_rms; the BACnet user's manual 1040E2102 lists them, without units.

// free download

The Acuvim II workspace

One dashboard page for an Acuvim II on a 400 V board: the three-phase meter element with voltages, currents, power, power factor and energy, total power against demand, neutral current, unbalance, current THD per phase and a trend.

BACManager dashboard for an Accuenergy Acuvim II on a distribution board: the three-phase meter with phase voltages near 230 V, currents, power and power factor per phase, total active power and demand, reactive power, neutral current, unbalance, import energy, a current THD table and a trend of total power stepping as a compressor stage cycles
Total power steps as a compressor stage cycles; the demand follows slowly (simulated meter)
1

Discover the meter

On the BACnet tab open MS/TP on the PC's RS-485 port at the meter's baud rate (or BACnet/IP for an AXM-WEB2) and press Discover. The meter appears with the ID from S52.

2

Open the workspace

Workspace → Open. The file reads device 41001; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.

3

Nothing to write

BACManager polls the meter by itself — the meter has no COV to subscribe to. Change the nominal voltage and rated current on the meter element to your board's.

Download workspace
// when it does not work

Typical problems

What you seeWhyWhat to do
The meter never answers Who-IsS38 Protocol 1 still ModbusS38 = BACNET
Answers, but every AI is unknownAn AXM-BMS module: AV0–AV55, not AI1–AI71Read the object list; bind to the AVs
Silent for a minute after power-upIIV3-M from firmware 6.20: 60 s of Modbus 9600Wait the minute
Writes or COV subscriptions refusedSmart Sensor profile: read only, no COVPoll; clear energy on the meter
Two meters with one instanceS52 never setA unique S52 on each meter
Bad frames at 19200Trunk at another baud rateS02 to the trunk's rate
// questions

Acuvim II BACnet — FAQ

How do I switch an Acuvim II to BACnet?+
In Settings → SYS: set the address in S01, the baud rate in S02, Protocol 1 = BACNET in S38, Max Info Frames in S51 and a unique device ID in S52, each accepted with V/A.
What are the Acuvim II BACnet objects?+
71 Analog Inputs, AI1 Frequency to AI71 Average Current THD: voltages, currents, power, power factor, demand, energy and THD, with units. Meters with the older AXM-BMS module serve AV0–AV55 instead.
Can I write to the Acuvim II over BACnet?+
No. The BTL listing gives it the Smart Sensor profile: reading and discovery only, no WriteProperty and no COV.
What is the default baud rate?+
19200 on the meter's own port. The older AXM-BMS module leaves the factory at 9600.
Does the Acuvim II support BACnet/IP?+
Through the AXM-WEB2 module (older meters: AXM-BIP), configured in its web page with port 47808 by default, a device instance and an optional BBMD registration.
// sources

Where this comes from

Accuenergy: Acuvim II Series Power Meter User Manual V3.2.17, section 6.4 and Table 6-85; BACnet for Acuvim II Series Power Meter User's Manual, document 1040E2102, V2.0.1 (August 2023); BTL listing BTL-30936 (Acuvim II series, version 6.08). Get them from accuenergy.com and check them against your meter's firmware. No factory device ID or Max Master setting is given for the native port. Accuenergy and Acuvim are trademarks of their owner; BACManager is not affiliated with Accuenergy. The pictures on this page are from BACManager connected to a simulated meter built from the published object table.

// more device guides

Other BACnet devices

Chillers and rooftop units
Daikin MicroTech III chiller
Trane Symbio 700
Carrier AquaSnap 30RC
York YLAA chiller
AAON VCCX2
Lennox CORE
Air handling units
Swegon GOLD
Systemair Access (Geniox, Topvex)
VAV and room controllers
KMC Conquest VAV
Data centre cooling
Vertiv Liebert iCOM
Boilers
Lochinvar Crest boiler
VRF and split systems
Daikin iTM (VRV)
Mitsubishi AE-200
Drives
ABB ACH580
Schneider ATV600
Siemens SINAMICS G120P
Danfoss VLT FC 102
Yaskawa HV600
Pumps and valves
Grundfos MAGNA3 (CIM)
Wilo Stratos MAXO (CIF)
Belimo Energy Valve
Routers
BASrouter (MS/TP to IP)

All BACnet device guides →

Read the meter from your laptop

Download the free trial, discover the meter and open the Acuvim II workspace — every phase on one meter element. No credit card.

Download free trial See pricing

Windows 10/11 · $149 one-time