Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: ModbusManager ↗
// york · johnson controls · ylaa scroll chiller · bacnet ms/tp

York YLAA
BACnet Points List & Setup

How to bring a York YLAA air-cooled scroll chiller onto a BMS over BACnet MS/TP: the native port on the IPU II micro panel and its keypad settings (where the device instance is an address times 100 plus an offset), the SC-EQ communication card that replaces E-Link, York's native data map — and the Local/Remote option that decides whether the chiller listens to the BMS at all. With a free BACManager workspace.

Download free trial Free YLAA workspace

Source: York IOM form 150.72-NM1 (110), YLAA0070–0175 Style A, and Johnson Controls form 450.50-N1 (222), SC-EQ Communication Card

// before you start

Native port or SC-EQ card

🔌

Native on the micro panel

A YLAA with the IPU II board speaks BACnet MS/TP on port 1 (terminal TB1, + and −) and Modbus RTU on port 2 (TB2 RS-485 or TB3 RS-232). York's IOM says no microgateway or E-Link is needed for these two. For BACnet/IP put a BACnet router in front of the trunk, or read MS/TP from a PC — see BACnet MS/TP over RS-485.

📡

Or the SC-EQ card

The SC-EQ communication card supersedes the E-Link gateway. For a YLAA (02550 micro board) it goes into the panel with kit 392-41230-001, which includes a transformer. JCI notes that a chiller with native communications needs no SC-EQ when it only talks to a BAS and Connected Services is not installed.

📋

What the chiller serves

York's data map lists the object types the native port uses: analog and binary inputs, outputs and values, the device and notification. A PICS, BTL listing, segmentation or Max APDU for the native port or the SC-EQ: not found in these documents. Keep requests small; BACManager splits ReadPropertyMultiple by itself.

// setup

Native BACnet from the keypad

On the micro panel press PROGRAM, DOWN four times, then ENTER. Values from the IOM's Tables 28 and 29.

SettingFactoryFor BACnet MS/TP
DE MODIFIER ADDRESS−10–41943; multiplied by 100
DE MODIFIER OFFSET−10–99; added to it. Device instance = address × 100 + offset, e.g. 120 and 1 give 12001
P1 PROTOCOLBACNETBACNET (API is for YorkTalk 2)
P1 MANUAL MAC ADDRESS−10–127, unique on the trunk
P1 BAUD RATE48009600–76800 or AUTO — 4800 is not a BACnet MS/TP rate
P1 PARITY / STOP BITSNONE / 1NONE / 1

The panel needs a power cycle after the settings change. If BACnet does not come up, the same menu shows REAL TIME ERROR; error 15 is “BACNET SETUP FAILED”. Modbus RTU on port 2 needs operating software C.MMC.13.03 or later (P2 PROTOCOL MODBUS SVR, 19200, no parity, one stop bit, RS-485 or RS-232). The IOM gives no factory device name.

With an SC-EQ card instead

SettingWhereWhat JCI gives
MAC address8-way DIP switch SW-1 (switch 8 unused)1–127, binary weighted; 0 if the BAS address is not known at commissioning. “The only user setting”
Protocol, baud, chiller modelAutomaticBACnet MS/TP, Modbus RTU or N2 detected on the BAS port J12; up to 120 s after power-up
Device instanceAutomatic5000 + MAC (MAC 6 = 5006). To change: SC-AP over Wi-Fi, BACNET DEVICE INSTANCE MODE = MANUAL, then SC-EQUIP BACNET INSTANCE ID; or BV65000 = 1 and AV65000 from the BAS
Device name, encodingFrom the BASSV65000; MV65003 (0 UCS-2, 1 ASCII)
UnitsSC-AP or MV650010 Imperial, 1 Metric — what the BAS sees, whatever the chiller displays
Chiller side (YLAA, IPU II)Micro panel keypadP1 PROTOCOL API, baud 4800, parity ODD, DE MODIFIER ADDRESS / OFFSET and P1 MAC −1; Local/Remote = Remote to send commands; cycle power

Turn the BAS EOL switch S2 on only when the SC-EQ is at an end of the RS-485 trunk. On a two-wire BAS, JCI calls for a 100 Ω 1 W resistor between J12 COM and J10 COM to ground. Reboot the SC-EQ after changing addresses. The SC-EQ exposes only the points that apply to the chiller it detected; JCI does not publish that list in 450.50-N1, so read the object list rather than reuse the native map below.

// writing to the chiller

Remote first, then the setpoint

York's write points, read/write in the native data map:

ObjectObject nameRangeWhat it does
BV_1START_STOP0, 1Stop / start command
AV_1REM_SETP40–70 °FRemote cooling setpoint (water; glycol units go lower)
AV_3LOAD_LIMIT0, 1, 2Load limit stage: on 2- and 4-compressor units stage 1 = 50 %, one compressor per system; stage 2 only on 3-, 5- and 6-compressor units (33 or 40 %)
AV_4REM_CR°FCooling range, discharge air (condensing unit) mode only
AV_2, AV_5, BV_2, BV_3SP_REM_SP_S1/S2, SS_SYS1/2—Per-system suction pressure control units only
AV_6, AV_7REM_SP_HEAT, HP_MODE—Heat pump models only
L/R

Local ignores the BMS

Option 5, Local/Remote Control Type: in LOCAL the panel runs on its own values and ignores commands from remote devices and the RS-485 inputs, while still sending data. Program REMOTE under OPTIONS for start/stop, setpoint and load limit to act. BI_20 CNTL_MODE reads which one is set.

5

Five minutes for ISN

York says that in REMOTE a unit with no valid ISN (YorkTalk) transmission for 5 minutes reverts to its local values. The IOM does not say the same of native BACnet writes. Writing the commands again every 2 minutes covers both; BACManager's per-tag Refresh (s) does it, and the free workspace sets 120 s.

8

Which priority

York's data map gives no priority array or recommended priority for the write points. BACManager writes at priority 8 unless you choose another; read COOL_SETP (AI_40) to see the setpoint actually in force.

// the rules that bite

4800 baud, −1, and a power cycle

4800

Factory baud is YorkTalk's

P1 BAUD RATE leaves the factory at 4800, the YorkTalk 2 rate. York's BACnet column asks for 9600–76800 or AUTO. A chiller left at 4800 never joins a BACnet trunk.

×100

The instance is built

The device instance is DE MODIFIER ADDRESS × 100 + DE MODIFIER OFFSET, both −1 from the factory. Two chillers set to the same address and offset collide on Who-Is; with an SC-EQ, the instance is 5000 + MAC instead.

⏻

Only a reboot applies it

Communication settings on the IPU II take effect only after the panel's power is cycled; the SC-EQ should be rebooted after address changes too, and keeps polling an old chiller Modbus address until it is.

The data map depends on the chiller's firmware. The one below is York's Table 31 dated 2/25/2009 for operating software C.MMC.13.xx–16.xx (Style A, IPU II board 031-02630 with 031-02550); newer Style B YLAA units have their own map, and York points to its Equipment Integration website for the latest one.

// points list

The YLAA points a BMS uses

Native BACnet, York's object names, English units (°F, PSIG). AI and BI are read only; AV and BV are the write points above.

BACManager BACnet tab: device YLAA-CH1, instance 12001, with its York objects listed by name and polled: REM_SETP, LOAD_LIMIT, START_STOP, LCHLT, RCHLT, OAT, S1_SUCT_PR, S1_DSCH_PR, S1_OP_CODE, S1_C1_RUN, EVAP_PUMP, CNTL_MODE and the others
The chiller's objects by name in BACManager (simulated chiller built from York's native data map)
ObjectObject nameUnitWhat it is
AI_1 / AI_2LCHLT / RCHLT°FLeaving and return chilled liquid temperature
AI_5OAT°FAmbient air temperature
AI_40 / AI_42COOL_SETP / CONTROL_RG°FSetpoint and cooling range in force
AI_33CONTROL_MODE—0 leaving water, 1 return water, 2 discharge air, 3 suction pressure, 4 cooling, 5 heating
AI_8 / AI_9, AI_17 / AI_18S1_SUCT_PR / S1_DSCH_PR, S2_…PSIGSuction and discharge pressure per system
AI_7 / AI_16S1_RUN_TIME / S2_RUN_TIMEsSystem run time
AI_13 / AI_22, AI_14S1_AR_TIMER / S2_AR_TIMER, AC_TIMERsAnti-recycle timers; anti-coincidence timer
AI_24NUM_COMPScountNumber of compressors
AI_25 / AI_27S1_OP_CODE / S2_OP_CODEindexOperational code: 0 no abnormal condition, 6 remote shutdown, 9 no cool load, 11 anti-recycle timer active, 16 load limiting, 17 compressor(s) running…
AI_26 / AI_28S1_FLT_CODE / S2_FLT_CODEindexFault code per system (York's code table)
AI_30 / AI_32S1_FAN_STAGE / S2_FAN_STAGEcountCondenser fan stage
AI_34–AI_39AR_TIME, LCHLT_CUT, LOW_AMB_CUT, … H_DSCH_P_COs, °F, PSIGProgrammed anti-recycle time and cutouts
BI_1 / BI_2S1_ALARM / S2_ALARM0, 1System alarm
BI_5, BI_11 / BI_6, BI_12S1_C1_RUN, S1_C2_RUN / S2_C1_RUN, S2_C2_RUN0, 1Compressor running (BI_16 / BI_17 for compressor 3)
BI_3 / BI_4EVAP_HTR / EVAP_PUMP0, 1Evaporator heater and pump status
BI_7 / BI_13, BI_9S1_LLSV / S2_LLSV, S1_HGBV0, 1Liquid line solenoids, hot gas bypass
BI_15 / BI_22LEAD_SYS / AUTO_LL0, 1Lead system (0 sys 1, 1 sys 2); lead/lag manual or auto
BI_18 / BI_19CH_LIQ_TYPE / AMB_MODE0, 1Water or glycol; standard or low ambient
BI_20 / BI_21CNTL_MODE / DATA_UNIT0, 1Local or Remote; Imperial or SI

York's Modbus registers follow the same numbering: 513 + AI number, 1281 + BI number, 1025 + AV number, 1537 + BV number. In the IOM's PDF the units and descriptions of a few rows near the end of the analog list (AI_12, AI_22, AI_23) are shifted against their names; check those on the chiller. EEV, heat pump and R-407C points apply only to those models.

// free download

The YLAA workspace

One dashboard page for a YLAA on its native BACnet port: Local/Remote, the chiller with leaving and return water and four compressors, start/stop, the remote setpoint and load limit written every 2 minutes, the operational codes and alarms of both systems, pressures, anti-recycle timers and two trends.

BACManager dashboard for a York YLAA chiller: REMOTE and Imperial units at the top, the chiller with leaving and return chilled water and its compressors running, start/stop, remote setpoint and load limit commands, setpoint in force and ambient, operational codes and alarms of both systems, suction and discharge pressures, anti-recycle timers, and trends of chilled water against the setpoint and of the refrigerant pressures
The remote setpoint lowered from the page: COOL_SETP follows, compressors stage on the leaving water and the anti-recycle timers count down (simulated chiller)
1

Discover the chiller

On the BACnet tab open MS/TP on the PC's RS-485 port at the trunk's baud rate (or BACnet/IP behind a router) and press Discover. The chiller appears with the instance built from the DE modifier address and offset, or 5000 + MAC behind an SC-EQ.

2

Open the workspace

Workspace → Open. The file reads device 12001; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over. Behind an SC-EQ check the object list first: its points are the card's, not necessarily the native map's.

3

Remote, Run, set once

Check CNTL_MODE reads REMOTE. On the Dashboard press Run and set start/stop, setpoint and load limit once; they are written again every 2 minutes. After BACManager restarts, set them once more.

Download workspace
// when it does not work

Typical problems

What you seeWhyWhat to do
Chiller never appears on the trunkP1 BAUD RATE still 4800, MAC or DE modifier still −1, or no power cycle9600–76800 or AUTO, MAC and instance set, then cycle power
REAL TIME ERROR 15BACNET SETUP FAILEDRecheck the P1 settings and the instance, cycle power
Writes accepted, chiller ignores themPanel in LOCAL (BI_20 = 0)Program REMOTE under OPTIONS
Setpoint falls back to the panel's ownRemote values time out (stated for ISN after 5 minutes)Write again every 2 minutes (Refresh 120 s)
Load limit 2 does nothingStage 2 exists only on 3-, 5- and 6-compressor unitsUse stage 1 on 2- and 4-compressor units
Two chillers, one device instanceSame DE modifier address and offset (or same SC-EQ MAC)Unique address/offset per chiller; SC-EQ instance 5000 + MAC or manual
SC-EQ points read unreliableCommandable points stay unreliable until the BAS writes themWrite the setpoints once
After replacing an E-Link, many points offlineE-Link offered every possible point; the SC-EQ only the relevant onesDelete the E-Link device and rediscover
Values in the wrong units through an SC-EQSC-EQ units (MV65001) differ from the chiller'sMatch the SC-EQ units to the chiller's display units
// questions

York YLAA BACnet — FAQ

Does a York YLAA need a gateway for BACnet?+
Not one with the IPU II micro panel: it has native BACnet MS/TP on port 1 (TB1) and Modbus RTU on port 2. The SC-EQ communication card is the alternative that replaced E-Link, and is needed for JCI Connected Services.
How is the YLAA's BACnet device instance set?+
From the keypad (PROGRAM, DOWN four times, ENTER): DE MODIFIER ADDRESS × 100 + DE MODIFIER OFFSET. Both are −1 from the factory. Behind an SC-EQ the instance is 5000 + the card's MAC unless set manually.
What baud rate does the YLAA use for BACnet MS/TP?+
9600 to 76800 or AUTO, set in P1 BAUD RATE. The factory value is 4800, which is for YorkTalk 2, so it has to be changed before the chiller joins a BACnet trunk.
Which object sets the chilled water setpoint?+
AV_1 REM_SETP, 40–70 °F for water, with the panel in REMOTE. AI_40 COOL_SETP shows the setpoint in force; BV_1 START_STOP starts and stops the unit and AV_3 LOAD_LIMIT limits capacity.
Why does the chiller ignore BACnet writes?+
The Local/Remote option is set to LOCAL: the panel then ignores commands from remote devices and the RS-485 inputs but still sends its data. BI_20 CNTL_MODE shows the setting.
Is the data map the same on every YLAA?+
No. It depends on the firmware: this page follows York's 2009 map for Style A units (C.MMC.13–16). Newer Style B units have their own map in their IOM and on JCI's Equipment Integration website.
// sources

Where this comes from

Johnson Controls / York: YLAA0070–0175 Style A 60 Hz Air-Cooled Scroll Chillers, Installation, Operation and Maintenance, form 150.72-NM1 (110) — BACnet, Modbus and YorkTalk 2 communications, Tables 28–31 (native data map dated 2/25/2009), load limiting, setpoint limits and the Local/Remote option; and SC-EQ Communication Card Installation Instructions, form 450.50-N1 (222), issued 02/28/2022. Get the documents from docs.johnsoncontrols.com and check them against your chiller's style and firmware; the data map is marked as JCI's property and subject to change. A recommended write priority, a PICS and the SC-EQ's own point list for a YLAA are not in these documents. JCI prints the SC-EQ manual instance range as “1 to 4914302”, most likely meaning the BACnet maximum 4194302. York and Johnson Controls are trademarks of Johnson Controls; BACManager is not affiliated with Johnson Controls. The pictures on this page are from BACManager connected to a simulated chiller built from the published data map.

// more device guides

Other BACnet devices

Chillers and rooftop units
Daikin MicroTech III chiller
Trane Symbio 700
Carrier AquaSnap 30RC
AAON VCCX2
Lennox CORE
Air handling units
Swegon GOLD
Systemair Access (Geniox, Topvex)
VAV and room controllers
KMC Conquest VAV
Data centre cooling
Vertiv Liebert iCOM
Boilers
Lochinvar Crest boiler
VRF and split systems
Daikin iTM (VRV)
Mitsubishi AE-200
Drives
ABB ACH580
Schneider ATV600
Siemens SINAMICS G120P
Danfoss VLT FC 102
Yaskawa HV600
Pumps and valves
Grundfos MAGNA3 (CIM)
Wilo Stratos MAXO (CIF)
Belimo Energy Valve
Energy meters
Accuenergy Acuvim II
Routers
BASrouter (MS/TP to IP)

All BACnet device guides →

Commission the YLAA from your laptop

Download the free trial, discover the chiller and open the YLAA workspace — every point by name, setpoint and start/stop written again every 2 minutes. No credit card.

Download free trial See pricing

Windows 10/11 · $149 one-time