How to bring a York YLAA air-cooled scroll chiller onto a BMS over BACnet MS/TP: the native port on the IPU II micro panel and its keypad settings (where the device instance is an address times 100 plus an offset), the SC-EQ communication card that replaces E-Link, York's native data map — and the Local/Remote option that decides whether the chiller listens to the BMS at all. With a free BACManager workspace.
Source: York IOM form 150.72-NM1 (110), YLAA0070–0175 Style A, and Johnson Controls form 450.50-N1 (222), SC-EQ Communication Card
A YLAA with the IPU II board speaks BACnet MS/TP on port 1 (terminal TB1, + and −) and Modbus RTU on port 2 (TB2 RS-485 or TB3 RS-232). York's IOM says no microgateway or E-Link is needed for these two. For BACnet/IP put a BACnet router in front of the trunk, or read MS/TP from a PC — see BACnet MS/TP over RS-485.
The SC-EQ communication card supersedes the E-Link gateway. For a YLAA (02550 micro board) it goes into the panel with kit 392-41230-001, which includes a transformer. JCI notes that a chiller with native communications needs no SC-EQ when it only talks to a BAS and Connected Services is not installed.
York's data map lists the object types the native port uses: analog and binary inputs, outputs and values, the device and notification. A PICS, BTL listing, segmentation or Max APDU for the native port or the SC-EQ: not found in these documents. Keep requests small; BACManager splits ReadPropertyMultiple by itself.
On the micro panel press PROGRAM, DOWN four times, then ENTER. Values from the IOM's Tables 28 and 29.
| Setting | Factory | For BACnet MS/TP |
|---|---|---|
| DE MODIFIER ADDRESS | −1 | 0–41943; multiplied by 100 |
| DE MODIFIER OFFSET | −1 | 0–99; added to it. Device instance = address × 100 + offset, e.g. 120 and 1 give 12001 |
| P1 PROTOCOL | BACNET | BACNET (API is for YorkTalk 2) |
| P1 MANUAL MAC ADDRESS | −1 | 0–127, unique on the trunk |
| P1 BAUD RATE | 4800 | 9600–76800 or AUTO — 4800 is not a BACnet MS/TP rate |
| P1 PARITY / STOP BITS | NONE / 1 | NONE / 1 |
The panel needs a power cycle after the settings change. If BACnet does not come up, the same menu shows REAL TIME ERROR; error 15 is “BACNET SETUP FAILED”. Modbus RTU on port 2 needs operating software C.MMC.13.03 or later (P2 PROTOCOL MODBUS SVR, 19200, no parity, one stop bit, RS-485 or RS-232). The IOM gives no factory device name.
| Setting | Where | What JCI gives |
|---|---|---|
| MAC address | 8-way DIP switch SW-1 (switch 8 unused) | 1–127, binary weighted; 0 if the BAS address is not known at commissioning. “The only user setting” |
| Protocol, baud, chiller model | Automatic | BACnet MS/TP, Modbus RTU or N2 detected on the BAS port J12; up to 120 s after power-up |
| Device instance | Automatic | 5000 + MAC (MAC 6 = 5006). To change: SC-AP over Wi-Fi, BACNET DEVICE INSTANCE MODE = MANUAL, then SC-EQUIP BACNET INSTANCE ID; or BV65000 = 1 and AV65000 from the BAS |
| Device name, encoding | From the BAS | SV65000; MV65003 (0 UCS-2, 1 ASCII) |
| Units | SC-AP or MV65001 | 0 Imperial, 1 Metric — what the BAS sees, whatever the chiller displays |
| Chiller side (YLAA, IPU II) | Micro panel keypad | P1 PROTOCOL API, baud 4800, parity ODD, DE MODIFIER ADDRESS / OFFSET and P1 MAC −1; Local/Remote = Remote to send commands; cycle power |
Turn the BAS EOL switch S2 on only when the SC-EQ is at an end of the RS-485 trunk. On a two-wire BAS, JCI calls for a 100 Ω 1 W resistor between J12 COM and J10 COM to ground. Reboot the SC-EQ after changing addresses. The SC-EQ exposes only the points that apply to the chiller it detected; JCI does not publish that list in 450.50-N1, so read the object list rather than reuse the native map below.
York's write points, read/write in the native data map:
| Object | Object name | Range | What it does |
|---|---|---|---|
| BV_1 | START_STOP | 0, 1 | Stop / start command |
| AV_1 | REM_SETP | 40–70 °F | Remote cooling setpoint (water; glycol units go lower) |
| AV_3 | LOAD_LIMIT | 0, 1, 2 | Load limit stage: on 2- and 4-compressor units stage 1 = 50 %, one compressor per system; stage 2 only on 3-, 5- and 6-compressor units (33 or 40 %) |
| AV_4 | REM_CR | °F | Cooling range, discharge air (condensing unit) mode only |
| AV_2, AV_5, BV_2, BV_3 | SP_REM_SP_S1/S2, SS_SYS1/2 | — | Per-system suction pressure control units only |
| AV_6, AV_7 | REM_SP_HEAT, HP_MODE | — | Heat pump models only |
Option 5, Local/Remote Control Type: in LOCAL the panel runs on its own values and ignores commands from remote devices and the RS-485 inputs, while still sending data. Program REMOTE under OPTIONS for start/stop, setpoint and load limit to act. BI_20 CNTL_MODE reads which one is set.
York says that in REMOTE a unit with no valid ISN (YorkTalk) transmission for 5 minutes reverts to its local values. The IOM does not say the same of native BACnet writes. Writing the commands again every 2 minutes covers both; BACManager's per-tag Refresh (s) does it, and the free workspace sets 120 s.
York's data map gives no priority array or recommended priority for the write points. BACManager writes at priority 8 unless you choose another; read COOL_SETP (AI_40) to see the setpoint actually in force.
P1 BAUD RATE leaves the factory at 4800, the YorkTalk 2 rate. York's BACnet column asks for 9600–76800 or AUTO. A chiller left at 4800 never joins a BACnet trunk.
The device instance is DE MODIFIER ADDRESS × 100 + DE MODIFIER OFFSET, both −1 from the factory. Two chillers set to the same address and offset collide on Who-Is; with an SC-EQ, the instance is 5000 + MAC instead.
Communication settings on the IPU II take effect only after the panel's power is cycled; the SC-EQ should be rebooted after address changes too, and keeps polling an old chiller Modbus address until it is.
The data map depends on the chiller's firmware. The one below is York's Table 31 dated 2/25/2009 for operating software C.MMC.13.xx–16.xx (Style A, IPU II board 031-02630 with 031-02550); newer Style B YLAA units have their own map, and York points to its Equipment Integration website for the latest one.
Native BACnet, York's object names, English units (°F, PSIG). AI and BI are read only; AV and BV are the write points above.
| Object | Object name | Unit | What it is |
|---|---|---|---|
| AI_1 / AI_2 | LCHLT / RCHLT | °F | Leaving and return chilled liquid temperature |
| AI_5 | OAT | °F | Ambient air temperature |
| AI_40 / AI_42 | COOL_SETP / CONTROL_RG | °F | Setpoint and cooling range in force |
| AI_33 | CONTROL_MODE | — | 0 leaving water, 1 return water, 2 discharge air, 3 suction pressure, 4 cooling, 5 heating |
| AI_8 / AI_9, AI_17 / AI_18 | S1_SUCT_PR / S1_DSCH_PR, S2_… | PSIG | Suction and discharge pressure per system |
| AI_7 / AI_16 | S1_RUN_TIME / S2_RUN_TIME | s | System run time |
| AI_13 / AI_22, AI_14 | S1_AR_TIMER / S2_AR_TIMER, AC_TIMER | s | Anti-recycle timers; anti-coincidence timer |
| AI_24 | NUM_COMPS | count | Number of compressors |
| AI_25 / AI_27 | S1_OP_CODE / S2_OP_CODE | index | Operational code: 0 no abnormal condition, 6 remote shutdown, 9 no cool load, 11 anti-recycle timer active, 16 load limiting, 17 compressor(s) running… |
| AI_26 / AI_28 | S1_FLT_CODE / S2_FLT_CODE | index | Fault code per system (York's code table) |
| AI_30 / AI_32 | S1_FAN_STAGE / S2_FAN_STAGE | count | Condenser fan stage |
| AI_34–AI_39 | AR_TIME, LCHLT_CUT, LOW_AMB_CUT, … H_DSCH_P_CO | s, °F, PSIG | Programmed anti-recycle time and cutouts |
| BI_1 / BI_2 | S1_ALARM / S2_ALARM | 0, 1 | System alarm |
| BI_5, BI_11 / BI_6, BI_12 | S1_C1_RUN, S1_C2_RUN / S2_C1_RUN, S2_C2_RUN | 0, 1 | Compressor running (BI_16 / BI_17 for compressor 3) |
| BI_3 / BI_4 | EVAP_HTR / EVAP_PUMP | 0, 1 | Evaporator heater and pump status |
| BI_7 / BI_13, BI_9 | S1_LLSV / S2_LLSV, S1_HGBV | 0, 1 | Liquid line solenoids, hot gas bypass |
| BI_15 / BI_22 | LEAD_SYS / AUTO_LL | 0, 1 | Lead system (0 sys 1, 1 sys 2); lead/lag manual or auto |
| BI_18 / BI_19 | CH_LIQ_TYPE / AMB_MODE | 0, 1 | Water or glycol; standard or low ambient |
| BI_20 / BI_21 | CNTL_MODE / DATA_UNIT | 0, 1 | Local or Remote; Imperial or SI |
York's Modbus registers follow the same numbering: 513 + AI number, 1281 + BI number, 1025 + AV number, 1537 + BV number. In the IOM's PDF the units and descriptions of a few rows near the end of the analog list (AI_12, AI_22, AI_23) are shifted against their names; check those on the chiller. EEV, heat pump and R-407C points apply only to those models.
One dashboard page for a YLAA on its native BACnet port: Local/Remote, the chiller with leaving and return water and four compressors, start/stop, the remote setpoint and load limit written every 2 minutes, the operational codes and alarms of both systems, pressures, anti-recycle timers and two trends.
On the BACnet tab open MS/TP on the PC's RS-485 port at the trunk's baud rate (or BACnet/IP behind a router) and press Discover. The chiller appears with the instance built from the DE modifier address and offset, or 5000 + MAC behind an SC-EQ.
Workspace → Open. The file reads device 12001; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over. Behind an SC-EQ check the object list first: its points are the card's, not necessarily the native map's.
Check CNTL_MODE reads REMOTE. On the Dashboard press Run and set start/stop, setpoint and load limit once; they are written again every 2 minutes. After BACManager restarts, set them once more.
| What you see | Why | What to do |
|---|---|---|
| Chiller never appears on the trunk | P1 BAUD RATE still 4800, MAC or DE modifier still −1, or no power cycle | 9600–76800 or AUTO, MAC and instance set, then cycle power |
| REAL TIME ERROR 15 | BACNET SETUP FAILED | Recheck the P1 settings and the instance, cycle power |
| Writes accepted, chiller ignores them | Panel in LOCAL (BI_20 = 0) | Program REMOTE under OPTIONS |
| Setpoint falls back to the panel's own | Remote values time out (stated for ISN after 5 minutes) | Write again every 2 minutes (Refresh 120 s) |
| Load limit 2 does nothing | Stage 2 exists only on 3-, 5- and 6-compressor units | Use stage 1 on 2- and 4-compressor units |
| Two chillers, one device instance | Same DE modifier address and offset (or same SC-EQ MAC) | Unique address/offset per chiller; SC-EQ instance 5000 + MAC or manual |
| SC-EQ points read unreliable | Commandable points stay unreliable until the BAS writes them | Write the setpoints once |
| After replacing an E-Link, many points offline | E-Link offered every possible point; the SC-EQ only the relevant ones | Delete the E-Link device and rediscover |
| Values in the wrong units through an SC-EQ | SC-EQ units (MV65001) differ from the chiller's | Match the SC-EQ units to the chiller's display units |
Johnson Controls / York: YLAA0070–0175 Style A 60 Hz Air-Cooled Scroll Chillers, Installation, Operation and Maintenance, form 150.72-NM1 (110) — BACnet, Modbus and YorkTalk 2 communications, Tables 28–31 (native data map dated 2/25/2009), load limiting, setpoint limits and the Local/Remote option; and SC-EQ Communication Card Installation Instructions, form 450.50-N1 (222), issued 02/28/2022. Get the documents from docs.johnsoncontrols.com and check them against your chiller's style and firmware; the data map is marked as JCI's property and subject to change. A recommended write priority, a PICS and the SC-EQ's own point list for a YLAA are not in these documents. JCI prints the SC-EQ manual instance range as “1 to 4914302”, most likely meaning the BACnet maximum 4194302. York and Johnson Controls are trademarks of Johnson Controls; BACManager is not affiliated with Johnson Controls. The pictures on this page are from BACManager connected to a simulated chiller built from the published data map.
Download the free trial, discover the chiller and open the YLAA workspace — every point by name, setpoint and start/stop written again every 2 minutes. No credit card.
Windows 10/11 · $149 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off.