Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: ModbusManager ↗
// yaskawa · hv600 hvac drive · embedded bacnet ms/tp

Yaskawa HV600
BACnet Points List & Setup

How to put a Yaskawa HV600 drive on BACnet MS/TP through its built-in RS-485 terminals: H5-08 = 3, a device instance written in hexadecimal across two parameters (factory: 1), the run and reference sources that leave the factory on terminals and analog input — and the bitmapped objects that must not be mixed with the single-bit ones. With a free BACManager workspace.

Download free trial Free HV600 workspace

Source: Yaskawa HV600 Drive Technical Reference SIEPC71061732F (revision 5, February 2024, drive software PRG 01018), section 6.3 “BACnet Communications”, with its PICS and BTL listing BTL-30529

// before you start

BACnet MS/TP is built into the HV600

🔌

No option card for MS/TP

The HV600 speaks BACnet MS/TP on terminal block TB6 as a B-ASC; up to 127 drives per MS/TP segment, more behind a router. BACnet/IP needs the JOHB-SMP3 option, which has its own, different object list — this page is about the embedded MS/TP port. For BACnet/IP without the option put a BACnet router in front of the trunk, or read MS/TP directly from a PC — see BACnet MS/TP over RS-485.

⚡

Wiring

TB6: D+ and D− for the data pair, AC for signal ground. Shielded cable, shield to the drive's ground terminal, kept apart from power wiring. DIP switch S2 ON switches in the built-in terminating resistor — on the drives at both physical ends only, OFF on all others. Bias: not given.

📋

What the drive serves

Per the PICS and BTL-30529 (firmware 2.01, BACnet revision 14): ReadProperty, ReadPropertyMultiple, WriteProperty, WritePropertyMultiple, COV and COVP, dynamic binding, DeviceCommunicationControl, ReinitializeDevice, TimeSynchronization. The PICS gives no segmentation window, so plan for none; max APDU: not given.

// setup

H5-08 = 3, then address, baud and instance

ParameterFactorySet to
H5-08 Communication Protocol Selection0 Modbus/MEMOBUS3 BACnet
H5-01 Drive Node Address1F hex (31)A free MS/TP MAC address. Entered in hex: MAC 12 is 0C
H5-02 Communication Speed3 = 96003, 4, 5 or 7 = 9600, 19200, 38400, 76800 — the BACnet rates
H5-03 Parity0 no parityLeave at 0; MS/TP frames have no parity
H5-14 / H5-15 Device Obj ID LOW / HIGH BITS0001 / 0000The device instance as a hex number split in two words: 6001 = 1771 hex → H5-14 = 1771, H5-15 = 0000. Range 0–4194302
H5-23 BACnet Max Master7F (127)The highest master MAC on the trunk, in hex
H5-24 BACnet Max Info Frames31–255; usually leave
H5-12 Run Command Method00 FWD/Stop, REV/Stop — the setting the BACnet section asks for
b1-01 / b1-021 Analog / 7 AUTO + Term Runb1-01 = 2 Serial; b1-02 = 2 Serial, or 8 AUTO Command + Serial Run
H5-04 / H5-05 / H5-093 Alarm Only / 1 / 2.0 sWhat a communication loss does — see the rules below

Yaskawa's procedure: set the H5 parameters, then switch the drive off and wait until the keypad display is dark, or set H5-20 = 1 Reload Now — but H5-20 reloads only H5-01, H5-02, H5-03 and H5-06. The manual says other parameter changes and a new Device Object Name take effect only after the drive is de-energised, so power-cycle after setting the instance. The Device Object Name (20 characters) and Location are written over BACnet, not on the keypad.

// control

Run FWD Cmd, Frequency Cmd in Hz — or the bitmap

The command objects are bits of the drive's command register 0001, as Yaskawa's object table lists. The frequency reference is in Hz (unit per o1-03), not in percent.

ObjectObject nameRegisterTo run
BV1Run FWD Cmd0001 bit 0RUN (1) forward; OFF stops
BV2Run REV Cmd0001 bit 1REV (1) reverse — never together with BV1
AV2Frequency Cmd00020.00–600.00 Hz, limited by the drive's maximum frequency
BV4Fault Reset Cmd0001 bit 3RESET (1) resets a fault
AV1Operation Cmd0001The same register as one bitmap, 0–2047
!

Bits or bitmap, not both

Yaskawa: when you use AV1 Operation Cmd, do not use BV1–BV11 or AV5; when you use AV5 Reference Select Cmd, do not use AV1, BO4 or BV9–BV11; when you use AV4 MF Output Cmd, do not use BO1–BO3 or BV12. They write the same registers. The workspace uses the single bits.

OR

Inputs are ORed

The multi-function input commands from BACnet (AV1 bits 4–A, BV7–BV11) and the drive's terminals S1–S7 are combined with a logical OR. A terminal that is on cannot be switched off from BACnet.

✋

HAND, OFF, AUTO

With b1-02 = 8 the drive takes BACnet's run command in AUTO mode only; HAND on the keypad uses the keypad reference. BV43 Run Command Mode and BV42 Frequency Ref Mode read COM or LOCAL. AV39 Drive HOA Status exists, but its values are not given in the manual.

// the rules that bite

Factory sources, hex instance, comm loss

b1

Not on serial from the factory

b1-01 is Analog Input and b1-02 AUTO Command + Term Run out of the box. BACnet reads everything, writes are accepted — and the motor follows terminals and analog input. Set b1-01 = 2 and b1-02 = 2 or 8.

#1

Every drive is instance 1

H5-14 = 0001 and H5-15 = 0000 on every new HV600. The instance is entered in hex: typing “6001” into H5-14 gives instance 24577 (6001 hex). Convert first.

CE

Communication loss

With H5-05 = 1 the drive flags CE when no data arrives from the master within H5-09 (2.0 s). H5-04 decides: 3 Alarm Only from the factory — the fan keeps running at the last command; 0 ramp, 1 coast, 2 fast stop (a fault); 4 run at H5-34. The manual calls it a Modbus error but lists these parameters in the BACnet setup.

// points list

The HV600 points a BMS uses

The embedded MS/TP list from the Technical Reference. Object names as the network displays them (the manual also gives a longer name). C = commandable (priority array), W = writable, R = read only. The drive's Modbus register is in brackets.

BACManager BACnet tab: device HV600-EF1, instance 6001, with its Yaskawa objects listed by name and polled: Output Frequency, Output Current, Output Power, DC Bus Voltage, Frequency Cmd, Run FWD Cmd, RUN-STOP, READY, FAULT, Current Sys Flt and the others
The drive's objects by name in BACManager (simulated drive built from Yaskawa's embedded MS/TP object table)
ObjectObject nameAccessWhat it is
BV1 / BV2 / BV4Run FWD Cmd / Run REV Cmd / Fault Reset CmdCRun forward, reverse, reset (0001 bits 0, 1, 3)
BV3Ext Fault CmdCExternal fault EF0 (0001 bit 2)
BV5 / BV6Com Net Cmd / Com Cntrl CmdCTexts COM / LOCAL; what they switch is not described
AV2 / AV3Frequency Cmd / PI Setpoint CmdCHz (0002); PID setpoint 0–100.00 % (0006)
AV1 / AV4 / AV5Operation Cmd / MF Output Cmd / Reference Select CmdCBitmaps (0001 / 0009 / 000F) — see “bits or bitmap”
BV13 / BV14 / BV15 / BV16RUN-STOP / REV-FWD / READY / FAULTRRunning, direction, ready, faulted (0020 bits 0–3)
BV33 / BV34 / BV35Operating / Zero Speed / Frequency AgreeR002C bits 0–2
BV42 / BV43Frequency Ref Mode / Run Command ModeRLOCAL (active) or COM (002C bits 9, 10)
BV18–BV32OverCurrent- Gnd Flt … Communication ErrorROne fault group each (0021)
BI28 / BI29Drive Fault Status / Drive Alarm StatusRFault; minor fault / alarm (004B bits 7, 6)
AV10 / AV9Output Frequency / Frequency ReferenceRHz (0041 / 0040)
AV36 / AV37Output Freq in % / Output Freq in RPMR% (003F), rpm (003E)
AV12 / AV13 / AV11Output Current / Output Power / Output VoltageRA (0026), kW (0047), V (0045)
AV18 / AV14 / AV38DC Bus Voltage / Torque Reference / Torque IQ (U6-01)RV (0031); % (0048 / 0051)
AV33 / AV35kWh Consumed / Drive Run TimeRkWh (005C–005D), h (004C)
AV42 / AV40Current Sys Flt / Last Drive FaultRFault code (0080 / 0081), table below
AV6 / AV7 / AV16Drive Status / Fault Details / Drive Status 2RBitmaps (0020 / 0021; Drive Status 2: register not given)
AV19 / AV20 / AV21PI Feedback Level / PI Input Level / PI Output LevelRPID loop, %
AV27 / AV28Accel Time / Decel TimeWC1-01 / C1-02, 0.1–6000.0 s (factory 30.0 s)
AV29 / AV30, BV55 / BV56Parameter Number / Parameter Data, Parameter Accept / Parameter EnterWAny drive parameter by its Modbus register — below
AI1 / AI2, AI9Drv Anlog In 1 Level / 2, Rated Current n9-01RAnalog inputs, %; drive rated current, A
BI1–BI7, BI8 / BI9Input Terminal 1…7, Multi Function Out 1 / 2RThe drive's own I/O
AO1 / AO2, BO1–BO3Drv Anlg Out1 Level…, MF Output, M1 - M2…COutputs driven from BACnet
BV60 / BV63Em Over DRV REV CMD / Em Over DRV FWD CMDCEmergency override run
Code (hex)As a numberFault
0002 / 00082 / 8Uv1 DC bus undervoltage / ov overvoltage
0006 / 00076 / 7GF ground fault / oC overcurrent
000A / 000B / 000C10 / 11 / 12oH1 heatsink overheat / oL1 motor overload / oL2 drive overload
001C / 001E28 / 30LF output phase loss / oPr keypad connection
0021 / 0022 / 002733 / 34 / 39CE communication error / bUS option error / EF0 external fault

Fault codes from the Technical Reference's fault-trace table (a selection); that AV42 shows them as plain numbers is our reading. Parameters not in the list: write the Modbus register (decimal) to AV29, then read AV30; to write, put the value in AV30 and set BV55 (RAM) or BV56 (RAM and EEPROM — at most 100,000 times). COV works only on objects that are neither commandable nor writable. Commandable objects keep a priority array and the drive uses the highest-priority value; which priority a BMS should use, and the relinquish defaults, are not in the manual. BACManager writes at priority 8 unless you choose otherwise.

// free download

The HV600 workspace

One dashboard page for an HV600 on an exhaust fan: the drive faceplate with run, fault and the Hz reference, the fan, frequency, speed, current, power, both voltages, reference and run source, the communication error, HOA status, ramps, energy and a trend.

BACManager dashboard for a Yaskawa HV600 on an exhaust fan: run command from COM, no fault, the drive faceplate running at its Hz reference with frequency, current and power, the fan turning, output frequency, rpm, current, power, DC bus and output voltage values, frequency reference from COM, no communication error, accel and decel times, energy, and a trend where the frequency ramps up
Start and the Hz reference from the faceplate; the drive ramps on Accel Time (simulated drive)
1

Discover the drive

On the BACnet tab open MS/TP on the PC's RS-485 port at the H5-02 baud rate (or BACnet/IP behind a router) and press Discover. The drive appears with the instance from H5-14/H5-15, and its objects by name.

2

Open the workspace

Workspace → Open. The file reads device 6001; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.

3

AUTO, then Start

With b1-01 = 2, b1-02 = 8 and the keypad in AUTO, press Run on the Dashboard, then Start and the frequency on the faceplate. Run Command Mode should read COM.

Download workspace
// when it does not work

Typical problems

What you seeWhyWhat to do
BV1 is RUN, the motor does not startb1-02 still 7 (terminal run); keypad in HAND or OFF; BV43 reads LOCALb1-02 = 2 or 8, AUTO on the keypad
Frequency Cmd ignoredb1-01 still 1 (analog input)b1-01 = 2; check BV42 reads COM
Two drives answer as instance 1H5-14/H5-15 factory valueSet the instance on every drive, in hex
Instance is not the number you typedH5-14 is hexadecimalConvert: 6001 decimal = 1771 hex
New instance or name not activeApplied after de-energisingPower off until the keypad is dark, then on
EF alarm, the motor ramps downFWD and REV commanded together for more than 0.5 sUse BV1 or BV2, never both
CE alarm or faultNo data from the master within H5-09Check wiring, S2 at both ends, baud and parity; H5-09 longer for a slow trunk
The drive never answersWiring or transceiverSelf-diagnostics: H1-06 = 67, jumper S6–SN, power on; the keypad shows PASS
A COV subscription is refusedCOV only on objects that are not writable or commandablePoll the command objects
// questions

Yaskawa HV600 BACnet — FAQ

How do I enable BACnet on a Yaskawa HV600?+
Wire TB6 (D+, D−, AC), set H5-08 = 3 BACnet, H5-01 the MS/TP address, H5-02 the baud rate, H5-14/H5-15 the device instance in hex and H5-23 the highest master address, then power the drive off until the keypad is dark and on again.
What is the default BACnet device instance of an HV600?+
1 (H5-14 = 0001, H5-15 = 0000), on every drive. The factory node address H5-01 is 1F hex (31), the baud rate 9600, Max Master 127 and Max Info Frames 3.
Which object starts the HV600?+
BV1 Run FWD Cmd (BV2 for reverse), with the reference in AV2 Frequency Cmd in Hz — once b1-01 = 2 and b1-02 = 2, or 8 with the keypad in AUTO. AV1 Operation Cmd is the same command register as a bitmap; use one or the other.
What happens when the HV600 loses BACnet communication?+
After H5-09 (2.0 s) without data from the master it shows CE. From the factory H5-04 = 3 Alarm Only, so the drive keeps running; set H5-04 to 0, 1 or 2 to stop it, or 4 to run at the H5-34 frequency.
Does the HV600 support ReadPropertyMultiple and COV?+
Yes, per its PICS and BTL-30529: ReadPropertyMultiple, WritePropertyMultiple and COV. COV is available only on objects that are neither commandable nor writable.
Is this the same object list as the JOHB-SMP3 BACnet/IP option?+
No. This page uses the embedded MS/TP list from the HV600 Technical Reference. The JOHB-SMP3 option has its own manual and object list for BACnet/IP: much of it matches, but it adds objects such as a Network Port object and external-drive gateway values; check that manual if your drive has the option, or read the object list from the drive itself.
// sources

Where this comes from

Yaskawa: HV600 Drive Technical Reference SIEPC71061732F, revision 5, February 2024, drive software PRG 01018 — section 6.3 “BACnet Communications” (objects, device object, parameter access, PICS) and the H5 and b1 parameter descriptions; BACnet PICS PICS.HV600.01 (07/25/2018, firmware 2.01); BACnet International listing BTL-30529 (Commercial HVAC Drive HV600, firmware 2.01, tested October 2018). The JOHB-SMP3 BACnet/IP option is described in SIEP C730600 0MB and is not covered here. Get the documents from yaskawa.com and check them against your drive's software. Notes marked as our reading are ours, not Yaskawa statements. Yaskawa is a trademark of Yaskawa Electric Corporation; BACManager is not affiliated with Yaskawa. The pictures on this page are from BACManager connected to a simulated drive built from the published object table.

// more device guides

Other BACnet devices

Chillers and rooftop units
Daikin MicroTech III chiller
Trane Symbio 700
Carrier AquaSnap 30RC
York YLAA chiller
AAON VCCX2
Lennox CORE
Air handling units
Swegon GOLD
Systemair Access (Geniox, Topvex)
VAV and room controllers
KMC Conquest VAV
Data centre cooling
Vertiv Liebert iCOM
Boilers
Lochinvar Crest boiler
VRF and split systems
Daikin iTM (VRV)
Mitsubishi AE-200
Drives
ABB ACH580
Schneider ATV600
Siemens SINAMICS G120P
Danfoss VLT FC 102
Pumps and valves
Grundfos MAGNA3 (CIM)
Wilo Stratos MAXO (CIF)
Belimo Energy Valve
Energy meters
Accuenergy Acuvim II
Routers
BASrouter (MS/TP to IP)

All BACnet device guides →

Commission the HV600 from your laptop

Download the free trial, discover the drive and open the HV600 workspace — every point by name, run and Hz reference on the faceplate. No credit card.

Download free trial See pricing

Windows 10/11 · $149 one-time