How to put a SINAMICS G120P drive on BACnet MS/TP through the CU230P-2's own RS-485 port: macro 110, the address switch, the device instance that every drive leaves the factory with (1), Max Master 32, the one-second fieldbus monitoring behind fault F01910 — and the control-word bits that have to be set before RUN STOP CMD does anything. With a free BACManager workspace.
Source: Siemens SINAMICS G120 … Fieldbuses function manual A5E34229197B AG, edition 11/2020 (FW V4.7 SP13), section 5.5
The Control Units CU230P-2 HVAC and CU230P-2 BT speak BACnet MS/TP on their RS-485 port. Other G120 control units do not. For BACnet/IP put a BACnet router in front of the trunk, or read MS/TP directly from a PC — see BACnet MS/TP over RS-485.
RS-485 up to 1200 m. Terminate the first and the last node with the Control Unit's terminating-resistor switch, and keep those two powered. An external 24 V supply on the Control Unit keeps the bus alive when the mains is off. The connector pins and switch position are in the CU230P-2 operating instructions.
B-ASC: ReadProperty, ReadPropertyMultiple, WriteProperty, SubscribeCOV (32 at most, lost on a restart), dynamic device and object binding, DeviceCommunicationControl. Max APDU 480, no segmentation. BTL-listed (BTL-30064).
| Parameter | Factory / macro 110 | Set to |
|---|---|---|
| p0015 | — | 110 “BT Mac 10: BACnet MS/TP fieldbus” (BOP-2: MAc PAr P15 → P_F bAc). It sets p2030 = 5 (BACnet), p2020 = 8 (38400 bit/s), p2040 = 1000 ms |
| Address switch / p2021 | 0 | A free MS/TP MAC, 1–127. The DIP switch wins; p2021 can only be changed with the switch at 0 |
| p2025[0] Device instance | 1 | A device instance unique in the building. Every drive leaves the factory as instance 1 |
| p2025[3] Max Master | 32 | The highest master MAC on the trunk. A drive at MAC 40 is never polled for while this stays 32 |
| p2020 Baud rate | 8 = 38400 | 9600–76800, the trunk's rate |
| p2040 Fieldbus monitoring | 1000 ms | 0–1999999 ms. Longer than the gap between your BMS's messages to the drive, with margin; 0 switches it off |
| p2025[1] / [2], p2024[0] | 5 / 3, 6000 ms | Max Info Frames, APDU retries, APDU timeout — usually leave |
A new address or device name takes effect only after a full power cycle: switch off, wait until every LED is dark, switch on. The device name is preset at first power-up and kept in p7610 (also writable through Object_Name). p2027 picks German or English object texts, also after a power cycle. Siemens notes that the drive's “unit switchover” function is not permitted with BACnet.
Each BACnet command object is one bit of the drive's control word r0054, as Siemens' object table lists. Setpoint 1 comes as a percentage in AV17.
| Object | Object name | Bit | To run |
|---|---|---|---|
| BV93 | CTL OVERRIDE | r0054.10 | 1 — control via the fieldbus |
| BV27 | OFF2 | r0054.1 | 1 — no coast stop |
| BV28 | OFF3 | r0054.2 | 1 — no quick stop |
| BV26 | RUN ENA CMD | r0054.3 | 1 — enable operation |
| BV20 | RUN STOP CMD | r0054.0 | 1 — ON; 0 — stop on the ramp |
| AV17 | FREQ SP PCT | setpoint 1 | −199.99…199.99 % |
| BV22 | FAULT RESET | r0054.7 | 0 → 1 acknowledges a fault |
Siemens lists the bits but does not write out the order for BACnet. The “To run” column is how a SINAMICS control word works: without bit 10 the drive ignores the fieldbus, and bits 1–3 must be 1 before ON is accepted. Try it on the drive with the motor safe before you rely on it.
Of the reference speed p2000, which BACnet shows as RPM STPT 1 (AV16). With p2000 = 1500 rpm on a 4-pole 50 Hz motor, 100 % is 50 Hz. Check OUT FREQ HZ (AV0) against the drive's own display.
The operator panel's “Manual” mode has a higher priority than the BACnet override control. BV4 MANUAL AUTO reads AUTO or LOCAL; BV90 LOCAL LOCK can stop the panel from taking over.
Macro 110 sets p2040 to 1000 ms. If no process data reaches the drive within that time it stops with F01910. A BMS that polls a trunk of many drives every few seconds will trip it: Siemens says the more nodes, the longer p2040 must be.
Out of the box, two G120Ps on one network answer Who-Is with the same device instance. Set p2025[0] on each one before the BMS discovers them.
MS/TP masters pass the token only up to Max Master. With the factory 32 a drive at MAC 33 or above can be invisible to the others; set p2025[3] to the trunk's highest MAC.
Object names as Siemens lists them. C = commandable (priority array), W = writable, R = read only. The drive's parameter is in brackets.
| Object | Object name | Access | What it is |
|---|---|---|---|
| BV20 / BV21 / BV22 | RUN STOP CMD / FWD REV CMD / FAULT RESET | C | ON, reverse, acknowledge (r0054.0 / .11 / .7) |
| BV26 / BV27 / BV28 / BV93 | RUN ENA CMD / OFF2 / OFF3 / CTL OVERRIDE | C | The other control-word bits (r0054.3 / .1 / .2 / .10) |
| AV17 | FREQ SP PCT | C | Setpoint 1, % |
| BV0 / BV1 | RUN STOPPED / FWD REV | R | Running; direction, whatever the command source (r0052.2 / .14) |
| BV2 / BV3 | FAULT / WARN | R | Fault; warning (r0052.3 / .7) |
| BV4 / BV8 / BV10 | MANUAL AUTO / AT SETPOINT / DRIVE READY | R | AUTO or LOCAL; setpoint reached; ready |
| AV0 / AV1 / AV2 | OUT FREQ HZ / OUT FREQ PCT / OUTPUT SPEED | R | Hz, %, rpm |
| AV5 / AV6 / AV7 | CURRENT / TORQUE / POWER | R | A, N·m, kW (r0027 / r0031 / r0032) |
| AV3 / AV4 | DC BUS VOLT / OUTPUT VOLT | R | V |
| AV8 / AV9 | DRIVE TEMP / MOTOR TEMP | R | Heat sink and motor, °C |
| AV10 / AV12 | KWH NR / INV RUN TIME | R / W | Energy, kWh (cannot be reset); motor hours (write 0 to reset) |
| AV18 / AV19–22 | ACT FAULT / PREV FAULT 1–4 | R | Fault numbers, e.g. 1910 |
| AV39 / AV40–41 | ACT WARN / PREV WARN 1–2 | R | Alarm numbers |
| AV16 / AV30 / AV31 | RPM STPT 1 / MIN Speed / MAX Speed | W | Reference speed p2000; p1080 / p1082, rpm |
| AV32 / AV33 | ACCEL TIME / DECEL TIME | W | Ramp times p1120 / p1121, s |
| MSI0–7 / MSI8–15 | fault 1–8 / warning 1–8 | R | Fault and alarm buffers as multistate values |
| AI0–1, BI0–5, BI10–12 | ANALOG IN 0…, DI0 ACT…, DO0 ACT… | R | The drive's own I/O |
| BO0–2, AO0–1 | DO0 CMD…, ANALOG OUT 0… | C | Relays and analog outputs driven from BACnet |
| BV50–53, AV5000–5307 | ENABLE PID…, PROP GAIN… | C / W | The drive's technology controllers |
With BACnet the drive's analog outputs follow AO0/AO1 from the bus. To put a drive value on an output instead, connect it with p0771 — then writing that AO returns an error. Which BACnet priority a BMS should command at, and the relinquish defaults, are not in the manual; BACManager writes at priority 8 unless you choose otherwise.
One dashboard page for a G120P on a supply fan: the drive faceplate with run, fault and setpoint, the four control-word switches, frequency, speed, current, power, DC link, energy and a trend.
On the BACnet tab open MS/TP on the PC's RS-485 port at the trunk's baud rate (or BACnet/IP behind a router) and press Discover. The drive appears with the instance from p2025[0].
Workspace → Open. The file reads device 31010; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.
On the Dashboard press Run, set the four control-word switches to 1, then Start and the setpoint on the faceplate. BACManager keeps reading the drive, so p2040 sees a message at least every poll.
| What you see | Why | What to do |
|---|---|---|
| Drive stops with F01910 | No process data within p2040 (1000 ms after macro 110) | p2040 above the BMS's poll gap, with margin; or 0 if the BMS monitors the drive itself |
| RUN STOP CMD written, nothing happens | CTL OVERRIDE, OFF2, OFF3 or RUN ENA CMD still 0; or the panel is in Manual | Set BV93, BV27, BV28, BV26 to 1; check BV4 reads AUTO |
| Two drives answer as instance 1 | p2025[0] factory value | Set the device instance on every drive |
| A drive at a high MAC never appears | Max Master 32 on the other masters | p2025[3] = the trunk's highest MAC, on every master |
| New address or name ignored | Only a full power cycle applies them | Power off until all LEDs are dark, then on |
| Address p2021 cannot be changed | The address switch is not at 0 | Use the switch, or set it to 0 first |
| A large ReadPropertyMultiple is refused | Max APDU 480, no segmentation | Fewer properties per request (BACManager splits by itself) |
| COV updates stop after a drive restart | Subscriptions are not kept | Subscribe again, or poll those points |
Siemens AG: SINAMICS G120, G120P, G120C, G110M, G115D — Fieldbuses, Function Manual, edition 11/2020, firmware V4.7 SP13, A5E34229197B AG, section 5.5 “Communication via BACnet MS/TP”, and BTL listing BTL-30064 for the CU230P-2 HVAC and BT. Get the manual from Siemens Industry Online Support and check it against your drive's firmware. The run order of the control-word bits is our reading of the control word, not a Siemens statement. Siemens and SINAMICS are trademarks of Siemens AG; BACManager is not affiliated with Siemens. The pictures on this page are from BACManager connected to a simulated drive built from the published object table.
Download the free trial, discover the drive and open the G120P workspace — every point by name, the control-word bits on switches. No credit card.
Windows 10/11 · $149 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off.