Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: ModbusManager ↗
// siemens · sinamics g120p · cu230p-2 hvac / bt

Siemens G120P
BACnet Points List & Setup

How to put a SINAMICS G120P drive on BACnet MS/TP through the CU230P-2's own RS-485 port: macro 110, the address switch, the device instance that every drive leaves the factory with (1), Max Master 32, the one-second fieldbus monitoring behind fault F01910 — and the control-word bits that have to be set before RUN STOP CMD does anything. With a free BACManager workspace.

Download free trial Free G120P workspace

Source: Siemens SINAMICS G120 … Fieldbuses function manual A5E34229197B AG, edition 11/2020 (FW V4.7 SP13), section 5.5

// before you start

BACnet is built into the CU230P-2

🔌

No option card

The Control Units CU230P-2 HVAC and CU230P-2 BT speak BACnet MS/TP on their RS-485 port. Other G120 control units do not. For BACnet/IP put a BACnet router in front of the trunk, or read MS/TP directly from a PC — see BACnet MS/TP over RS-485.

⚡

Wiring

RS-485 up to 1200 m. Terminate the first and the last node with the Control Unit's terminating-resistor switch, and keep those two powered. An external 24 V supply on the Control Unit keeps the bus alive when the mains is off. The connector pins and switch position are in the CU230P-2 operating instructions.

📋

What the drive serves

B-ASC: ReadProperty, ReadPropertyMultiple, WriteProperty, SubscribeCOV (32 at most, lost on a restart), dynamic device and object binding, DeviceCommunicationControl. Max APDU 480, no segmentation. BTL-listed (BTL-30064).

// setup

Macro 110, then the address and the instance

ParameterFactory / macro 110Set to
p0015—110 “BT Mac 10: BACnet MS/TP fieldbus” (BOP-2: MAc PAr P15 → P_F bAc). It sets p2030 = 5 (BACnet), p2020 = 8 (38400 bit/s), p2040 = 1000 ms
Address switch / p20210A free MS/TP MAC, 1–127. The DIP switch wins; p2021 can only be changed with the switch at 0
p2025[0] Device instance1A device instance unique in the building. Every drive leaves the factory as instance 1
p2025[3] Max Master32The highest master MAC on the trunk. A drive at MAC 40 is never polled for while this stays 32
p2020 Baud rate8 = 384009600–76800, the trunk's rate
p2040 Fieldbus monitoring1000 ms0–1999999 ms. Longer than the gap between your BMS's messages to the drive, with margin; 0 switches it off
p2025[1] / [2], p2024[0]5 / 3, 6000 msMax Info Frames, APDU retries, APDU timeout — usually leave

A new address or device name takes effect only after a full power cycle: switch off, wait until every LED is dark, switch on. The device name is preset at first power-up and kept in p7610 (also writable through Object_Name). p2027 picks German or English object texts, also after a power cycle. Siemens notes that the drive's “unit switchover” function is not permitted with BACnet.

// control

The command objects are control-word bits

Each BACnet command object is one bit of the drive's control word r0054, as Siemens' object table lists. Setpoint 1 comes as a percentage in AV17.

ObjectObject nameBitTo run
BV93CTL OVERRIDEr0054.101 — control via the fieldbus
BV27OFF2r0054.11 — no coast stop
BV28OFF3r0054.21 — no quick stop
BV26RUN ENA CMDr0054.31 — enable operation
BV20RUN STOP CMDr0054.01 — ON; 0 — stop on the ramp
AV17FREQ SP PCTsetpoint 1−199.99…199.99 %
BV22FAULT RESETr0054.70 → 1 acknowledges a fault
!

Our reading, check it

Siemens lists the bits but does not write out the order for BACnet. The “To run” column is how a SINAMICS control word works: without bit 10 the drive ignores the fieldbus, and bits 1–3 must be 1 before ON is accepted. Try it on the drive with the motor safe before you rely on it.

%

AV17 is a percentage

Of the reference speed p2000, which BACnet shows as RPM STPT 1 (AV16). With p2000 = 1500 rpm on a 4-pole 50 Hz motor, 100 % is 50 Hz. Check OUT FREQ HZ (AV0) against the drive's own display.

✋

Hand wins

The operator panel's “Manual” mode has a higher priority than the BACnet override control. BV4 MANUAL AUTO reads AUTO or LOCAL; BV90 LOCAL LOCK can stop the panel from taking over.

// the rules that bite

One second, instance 1, Max Master 32

1 s

Fieldbus monitoring

Macro 110 sets p2040 to 1000 ms. If no process data reaches the drive within that time it stops with F01910. A BMS that polls a trunk of many drives every few seconds will trip it: Siemens says the more nodes, the longer p2040 must be.

#1

Every drive is instance 1

Out of the box, two G120Ps on one network answer Who-Is with the same device instance. Set p2025[0] on each one before the BMS discovers them.

32

Max Master 32

MS/TP masters pass the token only up to Max Master. With the factory 32 a drive at MAC 33 or above can be invisible to the others; set p2025[3] to the trunk's highest MAC.

// points list

The G120P points a BMS uses

Object names as Siemens lists them. C = commandable (priority array), W = writable, R = read only. The drive's parameter is in brackets.

BACManager BACnet tab: device G120P-SF1, instance 31010, with its SINAMICS objects listed by name and polled: OUT FREQ HZ, OUTPUT SPEED, CURRENT, POWER, DC BUS VOLT, RUN STOPPED, FAULT, DRIVE READY, RUN STOP CMD, CTL OVERRIDE and the others
The drive's objects by name in BACManager (simulated drive built from Siemens' object table)
ObjectObject nameAccessWhat it is
BV20 / BV21 / BV22RUN STOP CMD / FWD REV CMD / FAULT RESETCON, reverse, acknowledge (r0054.0 / .11 / .7)
BV26 / BV27 / BV28 / BV93RUN ENA CMD / OFF2 / OFF3 / CTL OVERRIDECThe other control-word bits (r0054.3 / .1 / .2 / .10)
AV17FREQ SP PCTCSetpoint 1, %
BV0 / BV1RUN STOPPED / FWD REVRRunning; direction, whatever the command source (r0052.2 / .14)
BV2 / BV3FAULT / WARNRFault; warning (r0052.3 / .7)
BV4 / BV8 / BV10MANUAL AUTO / AT SETPOINT / DRIVE READYRAUTO or LOCAL; setpoint reached; ready
AV0 / AV1 / AV2OUT FREQ HZ / OUT FREQ PCT / OUTPUT SPEEDRHz, %, rpm
AV5 / AV6 / AV7CURRENT / TORQUE / POWERRA, N·m, kW (r0027 / r0031 / r0032)
AV3 / AV4DC BUS VOLT / OUTPUT VOLTRV
AV8 / AV9DRIVE TEMP / MOTOR TEMPRHeat sink and motor, °C
AV10 / AV12KWH NR / INV RUN TIMER / WEnergy, kWh (cannot be reset); motor hours (write 0 to reset)
AV18 / AV19–22ACT FAULT / PREV FAULT 1–4RFault numbers, e.g. 1910
AV39 / AV40–41ACT WARN / PREV WARN 1–2RAlarm numbers
AV16 / AV30 / AV31RPM STPT 1 / MIN Speed / MAX SpeedWReference speed p2000; p1080 / p1082, rpm
AV32 / AV33ACCEL TIME / DECEL TIMEWRamp times p1120 / p1121, s
MSI0–7 / MSI8–15fault 1–8 / warning 1–8RFault and alarm buffers as multistate values
AI0–1, BI0–5, BI10–12ANALOG IN 0…, DI0 ACT…, DO0 ACT…RThe drive's own I/O
BO0–2, AO0–1DO0 CMD…, ANALOG OUT 0…CRelays and analog outputs driven from BACnet
BV50–53, AV5000–5307ENABLE PID…, PROP GAIN…C / WThe drive's technology controllers

With BACnet the drive's analog outputs follow AO0/AO1 from the bus. To put a drive value on an output instead, connect it with p0771 — then writing that AO returns an error. Which BACnet priority a BMS should command at, and the relinquish defaults, are not in the manual; BACManager writes at priority 8 unless you choose otherwise.

// free download

The G120P workspace

One dashboard page for a G120P on a supply fan: the drive faceplate with run, fault and setpoint, the four control-word switches, frequency, speed, current, power, DC link, energy and a trend.

BACManager dashboard for a Siemens SINAMICS G120P on a supply fan: AUTO, no fault, the drive faceplate running at its setpoint with frequency, current and power, the four control-word switches at 1, output frequency, motor speed, current, power and DC link values, and a trend where the frequency ramps up
CTL OVERRIDE, OFF2, OFF3, RUN ENA CMD set to 1, then Start and the setpoint from the faceplate; the drive ramps on ACCEL TIME (simulated drive)
1

Discover the drive

On the BACnet tab open MS/TP on the PC's RS-485 port at the trunk's baud rate (or BACnet/IP behind a router) and press Discover. The drive appears with the instance from p2025[0].

2

Open the workspace

Workspace → Open. The file reads device 31010; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.

3

Bits first, then Start

On the Dashboard press Run, set the four control-word switches to 1, then Start and the setpoint on the faceplate. BACManager keeps reading the drive, so p2040 sees a message at least every poll.

Download workspace
// when it does not work

Typical problems

What you seeWhyWhat to do
Drive stops with F01910No process data within p2040 (1000 ms after macro 110)p2040 above the BMS's poll gap, with margin; or 0 if the BMS monitors the drive itself
RUN STOP CMD written, nothing happensCTL OVERRIDE, OFF2, OFF3 or RUN ENA CMD still 0; or the panel is in ManualSet BV93, BV27, BV28, BV26 to 1; check BV4 reads AUTO
Two drives answer as instance 1p2025[0] factory valueSet the device instance on every drive
A drive at a high MAC never appearsMax Master 32 on the other mastersp2025[3] = the trunk's highest MAC, on every master
New address or name ignoredOnly a full power cycle applies themPower off until all LEDs are dark, then on
Address p2021 cannot be changedThe address switch is not at 0Use the switch, or set it to 0 first
A large ReadPropertyMultiple is refusedMax APDU 480, no segmentationFewer properties per request (BACManager splits by itself)
COV updates stop after a drive restartSubscriptions are not keptSubscribe again, or poll those points
// questions

Siemens G120P BACnet — FAQ

How do I enable BACnet on a SINAMICS G120P?+
Select macro 110 (p0015 = 110, “BT Mac 10: BACnet MS/TP fieldbus”), set the MS/TP address on the address switch or in p2021, set a unique device instance in p2025[0], and power the drive off until all LEDs are dark and on again.
What is the default BACnet device instance of a G120P?+
1, on every drive (p2025[0]). Max Master is 32 and the baud rate after macro 110 is 38400.
Why does the G120P trip F01910 on BACnet?+
Fieldbus monitoring p2040 is 1000 ms after macro 110: when no process data reaches the drive within that time it faults with F01910. Set p2040 longer than the gap between your BMS's messages to the drive.
Which object starts the drive?+
BV20 RUN STOP CMD is the ON bit of the control word. It works together with BV93 CTL OVERRIDE, BV27 OFF2, BV28 OFF3 and BV26 RUN ENA CMD, which need to be 1; the setpoint is AV17 FREQ SP PCT in percent.
Does the G120P support BACnet/IP?+
The CU230P-2 speaks BACnet MS/TP on its RS-485 port. Reach it from BACnet/IP through a BACnet router; BACManager also reads MS/TP directly from a USB RS-485 adapter.
Which other G120 control units have BACnet?+
The function manual describes BACnet MS/TP only for the CU230P-2 HVAC and CU230P-2 BT control units.
// sources

Where this comes from

Siemens AG: SINAMICS G120, G120P, G120C, G110M, G115D — Fieldbuses, Function Manual, edition 11/2020, firmware V4.7 SP13, A5E34229197B AG, section 5.5 “Communication via BACnet MS/TP”, and BTL listing BTL-30064 for the CU230P-2 HVAC and BT. Get the manual from Siemens Industry Online Support and check it against your drive's firmware. The run order of the control-word bits is our reading of the control word, not a Siemens statement. Siemens and SINAMICS are trademarks of Siemens AG; BACManager is not affiliated with Siemens. The pictures on this page are from BACManager connected to a simulated drive built from the published object table.

// more device guides

Other BACnet devices

Chillers and rooftop units
Daikin MicroTech III chiller
Trane Symbio 700
Carrier AquaSnap 30RC
York YLAA chiller
AAON VCCX2
Lennox CORE
Air handling units
Swegon GOLD
Systemair Access (Geniox, Topvex)
VAV and room controllers
KMC Conquest VAV
Data centre cooling
Vertiv Liebert iCOM
Boilers
Lochinvar Crest boiler
VRF and split systems
Daikin iTM (VRV)
Mitsubishi AE-200
Drives
ABB ACH580
Schneider ATV600
Danfoss VLT FC 102
Yaskawa HV600
Pumps and valves
Grundfos MAGNA3 (CIM)
Wilo Stratos MAXO (CIF)
Belimo Energy Valve
Energy meters
Accuenergy Acuvim II
Routers
BASrouter (MS/TP to IP)

All BACnet device guides →

Commission the G120P from your laptop

Download the free trial, discover the drive and open the G120P workspace — every point by name, the control-word bits on switches. No credit card.

Download free trial See pricing

Windows 10/11 · $149 one-time