Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: ModbusManager ↗
// danfoss · vlt hvac drive fc 102 · native bacnet ms/tp

Danfoss FC 102
BACnet Points List & Setup

How to put a VLT HVAC Drive FC 102 on BACnet MS/TP through its own RS-485 port, terminals 68 and 69: 8-30 Protocol = BACnet, the device instance every drive leaves the factory with (1), Max Masters 127, terminal 27 that coasts the motor whatever BACnet says — and the control timeout that counts writes, not reads. With a free BACManager workspace.

Download free trial Free FC 102 workspace

Sources: Danfoss VLT HVAC Drive Native BACnet Operating Instructions MG.14.C1.02, the FC 102 Programming Guides M0010001 (SW 5.41, 10/2019) and AU430028034214en-001901 (SW 7.61, 2024.10), BTL listing BTL-30670

// before you start

BACnet MS/TP is built into the FC 102

🔌

No option card for MS/TP

The drive's standard RS-485 “FC port” on the control card speaks BACnet MS/TP once 8-30 is set to BACnet. BACnet/IP needs the separate VLT BACnet/IP MCA 125 option, which has its own object list; or put a BACnet router in front of the trunk, or read MS/TP directly from a PC — see BACnet MS/TP over RS-485.

⚡

Wiring

Terminal 68 is P+, 69 is N−. Switch S801 BUS TER. terminates the port; it is OFF from the factory and must only be moved with the drive powered down. Daisy chain only — Danfoss allows no T-drops (use repeaters), 1200 m per segment, 100–130 Ω screened twisted pair, AWG 18, kept 200 mm from motor cables. Bias: not given.

📋

What the drive serves

BTL-30670 (firmware 1.11, BACnet revision 14): B-ASC with ReadProperty, WriteProperty, dynamic device and object binding, DeviceCommunicationControl, TimeSynchronization, ReinitializeDevice. No ReadPropertyMultiple and no COV are listed. Max APDU and segmentation: not given.

// setup

8-30 BACnet, then address, baud and instance

ParameterFactorySet to
8-30 Protocol[0] FC[5] BACnet. ([9] FC Option is for an external gateway on the port, not for native BACnet.) The 8-7* parameters appear once this is set
8-31 Address1A free MS/TP MAC, 1–127. The documents give the range three ways (1–127, 0–255, 1–255 “depends on protocol”)
8-32 Baud Ratesee note[2] 9600, [3] 19200, [4] 38400 or [6] 76800 — the only rates valid for BACnet. Set it; do not rely on the default
8-70 BACnet Device Instance1A device instance unique in the building, 0–4194302. It does not follow the MAC
8-72 MS/TP Max Masters127The highest master MAC on the trunk. Danfoss: lowering it speeds up the token passing
8-73 MS/TP Max Info Frames1Frames per token, 1–65534; usually leave
8-74 “I-Am” Service[0] at power-up[1] Continuously sends I-Am about once a minute
8-75 Initialisation Passwordsee noteThe password ReinitializeDevice needs
8-01 / 8-02[0] Digital and ctrl. word / FC port8-01 [0] or [2] Controlword only; 8-02 [1] FC Port
8-50 Coasting Select[3] Logic OR[1] Bus, or keep +24 V on terminal 27 — see the rules below

Danfoss' worked example sets 8-30, 8-31, 8-32, 8-50, 8-70 and 8-72, then says the drive must be switched off and on again before the changes apply. The documents do not agree on every factory value: for 8-32 the native-BACnet manual's setup table says 9600 while its parameter text marks 38400 and adds that the default belongs to the FC protocol; for 8-75 the setup table and the MCA 125 guide say “admin”, the parameter text shows 0, and the 2019 and 2024 programming guides only say “size related”. A BACnet value for 8-33 Parity / Stop Bits is not given. Check on your drive.

// control

RUN/STOP Command, a reference, and which one counts

The command objects write the drive's FC-profile control word, as Danfoss' object table lists. The reference is a percentage in AV:1 or AV:2 — only one of them is active, and BV:2 decides which.

ObjectObject nameControl wordTo run
BV:1RUN/STOP CommandCTW 047C (+ bit 15 reverse)1 — start; 0 — stop
BV:2REF 1 / REF 2 Select—Picks AV:1 or AV:2 as the reference
AV:1 / AV:2Input Reference 1 / Input Reference 2reference%, the active one
BV:3Fault Reset Commandbit 70 → 1 resets a trip
BV:24Coastingbit 3Leave alone unless you have tested which value coasts
MSV:1Active Setupbits 13, 14Selects set-up 1–4
!

Our reading, check it

Danfoss does not say which BV:2 state selects AV:1, which BV:24 state coasts, or what 100 % of AV:1 is (we assume the reference range, 0–50 Hz in our simulator). The FC 102 Design Guide (MG11BC02) defines the control-word bits: bit 3 at 0 coasts, the reset acts on the leading edge. Try it on the drive with the motor safe before you rely on it.

%

AV:3 is a percentage too

Output Speed is 16-17 Speed [RPM] divided by 4-13 Motor Speed High Limit [RPM], times 100 — not of the nominal speed. For Hz read AV:25 Frequency, for amps AV:5 Motor Current.

✋

Running is BV:33

BV:4 RUN / STOP Monitor is mapped to status-word bit 1, which the Design Guide calls drive ready. Whether the motor turns is BV:33 Running (bit 11). BV:32 Bus control (bit 9) is 0 when the drive is in local control and BACnet commands are ignored.

// the rules that bite

Terminal 27, the timeout, instance 1

27

Terminal 27 coasts

Terminal 27 is “Coast inverse” from the factory and needs +24 V before the drive will start; 8-50 Coasting Select is Logic OR, so an open terminal 27 coasts the motor whatever BV:1 says. Danfoss' BACnet text asks for 8-50 = Bus [1] or Logic AND [2], with 8-01 at [0] or [2] — although its own setup table lists Logic OR. Terminal 37 Safe Stop overrides everything.

17

Writes, not reads

With 8-04 Control Timeout Function set (factory Off), the drive acts when the control word is not updated within 8-03. The 2019 guide lists the BACnet objects that retrigger it: AOs, BOs, AV0, AV1, AV2, AV4, BV1–BV5, multistate outputs. A BMS that only reads trips alarm 17 Control word timeout. The old native-BACnet manual says 8-03/8-04 are not enabled at all in its version: firmware-dependent.

#1

Every drive is instance 1

8-70 is 1 from the factory, and Max Masters is 127. Two new FC 102s on one network answer Who-Is with the same instance. Set 8-70 on each one before the BMS discovers them.

// points list

The FC 102 points a BMS uses

Object names as Danfoss lists them (defaults: Danfoss marks the names writable, so a drive may show renamed points). C = commandable (priority array), W = writable, R = read only. The drive parameter or control/status-word bit is in brackets.

BACManager BACnet tab: device FC102-AHU1, instance 10201, with its Danfoss objects listed by name and polled: Input Reference 1, Output Speed, Motor Current, Power, Frequency, DC Link Voltage, Heatsink Temp., RUN/STOP Command, Running, Trip, Fault Code and the others
The drive's objects by name in BACManager (simulated drive built from Danfoss' object table)
ObjectObject nameAccessWhat it is
BV:1 / BV:3RUN/STOP Command / Fault Reset CommandC / WStart (CTW 047C); reset (bit 7)
BV:2REF 1 / REF 2 SelectCWhich reference is active
AV:1 / AV:2Input Reference 1 / 2CReference, %
BV:24 / BV:25 / BV:26 / BV:34Coasting / CW/CCW / Jog / Ramp 1/ Ramp 2CControl-word bits 3 / 15 / 8 / 9
BV:33 / BV:31Running / Speed = referenceRStatus-word bits 11 / 8
BV:21 / BV:22 / BV:23Warning / Trip / TriplockRStatus-word bits 7 / 3 / 6
BV:4 / BV:5RUN / STOP Monitor / OK / FAULT MonitorRStatus-word bit 1; bits 3, 6, 7 together
BV:6 / BV:32HAND / AUTO Reference / Bus controlR16-95 bit 1 (which state is Hand: read its Active_Text); status-word bit 9
AV:25 / AV:3Frequency / Output SpeedRHz (16-13); % of 4-13
AV:5 / AV:6 / AV:26Motor Current / Power / TorqueRA (16-14), kW (16-10), % (16-22)
AV:24 / AV:27Motor Voltage / DC Link VoltageRV (16-12 / 16-30)
AV:28 / AV:15 / AV:29Heatsink Temp. / Motor Thermal / Inverter ThermalR°C (16-34; the manual writes “Deg”); % (16-18 / 16-35)
AV:21 / AV:22 / AV:23Operating Hours / Running Hours / kWh CounterRh, h, kWh (15-00 / 15-01 / 15-02)
BV:28 / BV:29Reset KWh Counter / Reset Running Hours CounterW15-06 / 15-07
AV:51 / AV:50Fault Code / Alarm Log: Error CodeRBACnet fault code 1–21 (table below); last alarm number (15-30)
AV:4 / AV:30 / AV:31PID Feedback / Setpoint 1 / Bus Feedback 1R / W / W%, closed-loop PID (20-21, 8-94); also Setpoint 2/3, Bus Feedback 2/3 at AV:35–41
AV:52–57PID Start Speed … PID Diff. Gain LimitWPID tuning (20-83…20-96)
AI:0 / AI:1, BI:0–6Analog Input 53 / 54, Digital input Term 33…37RThe drive's own I/O (16-62 / 16-64, 16-60)
AO:0, BO:0/1, BO:4/5Terminal 42 Output Bus Control, Digital Output Term 27/29, Relay 1/2COutputs driven from BACnet
MSV:0 / MSV:1Smart Logic Controller State / Active SetupR / C16-38; set-up 1–4
AV:51FaultFC 102 alarms behind it
1Communication Error17 Control word timeout, 34 Fieldbus fault
2 / 3Over Current / Over Temperature13, 40–42, 59 / 11, 29, 65, 69, 74…
5 / 6Over Voltage / Under Voltage5, 7, 64 / 1, 6, 8
8 / 9Ground Fault / Motor Overload14 / 10, 50–58, 222
15 / 16 / 17Configuration Error / Feedback Failure / Output Phase Loss70, 76, 79… / 60, 90, 192 / 30, 31, 32
21Internal Drive Failure23, 27, 38, 39, 47, 48, 73, 85, 86

That is the mapping in MG.14.C1.02 (21 codes in all). The 2024 programming guide adds 8-76 VFD Fault Code Mapping New, Off from the factory: set to On, AV:51 follows the ASHRAE p-VFD fault codes instead — so check 8-76 before you build alarm texts. Priority_Array and Relinquish_Default exist on the BOs and on the commandable AO, AV, BV and MSV objects; which priority a BMS should use, and the relinquish defaults, are not in the documents. BACManager writes at priority 8 unless you choose otherwise.

// free download

The FC 102 workspace

One dashboard page for an FC 102 on an AHU supply fan: the drive faceplate with run, trip and reference, the fan, frequency, output speed, current, power, both voltages, reference select, hand/auto, triplock, thermal values, energy and a trend.

BACManager dashboard for a Danfoss VLT HVAC Drive FC 102 on an AHU supply fan: bus control, no fault, the drive faceplate running at its reference with frequency, current and power, the fan turning, frequency, output speed, motor current, power, DC link and motor voltage values, reference select, hand/auto and triplock, thermal, heatsink and energy values, and a trend where the frequency ramps up
Start and the reference from the faceplate; the drive ramps up while Input Reference 1 is re-written every 10 s for the control timeout (simulated drive)
1

Discover the drive

On the BACnet tab open MS/TP on the PC's RS-485 port at the 8-32 baud rate (or BACnet/IP behind a router) and press Discover. The drive appears with the instance from 8-70, and its objects by name.

2

Open the workspace

Workspace → Open. The file reads device 10201; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.

3

Timeout, then Start

The Input Reference 1 tag has Refresh (s) = 10: BACManager writes it again every 10 seconds, so set 8-03 well above that if you use 8-04. On the Dashboard press Run, then Start and the reference on the faceplate.

Download workspace
// when it does not work

Typical problems

What you seeWhyWhat to do
BV:1 is 1, the motor does not startNo +24 V on terminal 27 with 8-50 Logic OR; 8-01 Digital only; local control (BV:32 = 0); the other reference selected8-50 = Bus, or wire terminal 27; 8-01 [0] or [2]; Auto on the panel; check BV:2
Drive trips with alarm 17, AV:51 = 18-04 is set and nothing was written within 8-03 — reads do not count8-03 longer than the BMS's write interval, or re-write the reference (Refresh in BACManager)
Two drives answer as instance 18-70 factory valueSet the device instance on every drive
New settings ignoredBACnet settings apply after a power cycleSwitch the drive off and on
Group 8-7* not shown8-30 is not BACnet yetSet 8-30 = [5] BACnet first
The BMS gets an error to ReadPropertyMultipleBTL-30670 lists ReadProperty onlyPoll with ReadProperty
COV subscription refusedNo COV in the listingPoll those points
Fault codes do not match the table8-76 VFD Fault Code Mapping New is OnUse the ASHRAE p-VFD list, or set 8-76 Off
Drive clock wrong after a power cutThe real-time clock has no batteryLet the BMS send TimeSynchronization
// questions

Danfoss FC 102 BACnet — FAQ

How do I enable BACnet on a Danfoss FC 102?+
Wire the trunk to terminals 68 (P+) and 69 (N−), set 8-30 Protocol = [5] BACnet, 8-31 the MS/TP address (1–127), 8-32 the baud rate (9600, 19200, 38400 or 76800), 8-70 a unique device instance and 8-72 the highest master address, then switch the drive off and on.
What is the default BACnet device instance of an FC 102?+
1, on every drive (8-70). Max Masters 8-72 is 127 and Max Info Frames 8-73 is 1. The factory baud rate is given differently in different Danfoss documents, so set 8-32 explicitly.
Which object starts the drive?+
BV:1 RUN/STOP Command. The reference is AV:1 Input Reference 1 or AV:2 Input Reference 2, whichever BV:2 REF 1 / REF 2 Select chooses. 8-50 Coasting Select has to be Bus, or terminal 27 must carry +24 V, or the motor stays coasted.
Why does the FC 102 trip with alarm 17 on BACnet?+
8-04 Control Timeout Function is set and the control word was not updated within 8-03. On BACnet the timer is retriggered by writes to the command objects (AV1, AV2, BV1–BV5, outputs), not by reads. Make 8-03 longer than the BMS's write interval, or set 8-04 Off.
Does the FC 102 support ReadPropertyMultiple or COV?+
BTL listing BTL-30670 (firmware 1.11) lists neither: ReadProperty, WriteProperty and device-management services only. Plan for polling with ReadProperty.
Does the FC 102 support BACnet/IP?+
Not on the built-in port, which is MS/TP. Danfoss offers the VLT BACnet/IP MCA 125 option, which shares 8-70 with MS/TP and has its own object list. Or reach MS/TP through a BACnet router; BACManager also reads MS/TP directly from a USB RS-485 adapter.
// sources

Where this comes from

Danfoss A/S: VLT HVAC Drive Native BACnet Operating Instructions MG.14.C1.02 (undated, older firmware); VLT HVAC Drive FC 102 Programming Guide M0010001, software 5.41, 10/2019, and AU430028034214en-001901, software 7.61, 2024.10; FC 102 Design Guide MG11BC02, 06/2014 (control and status word); VLT BACnet/IP MCA 125 Programming Guide AU361182716349en-000201, 2025.12; and BACnet International listing BTL-30670 (VLT HVAC Drive FC102, firmware 1.11, tested July 2020). The native-BACnet manual is old and contradicts itself on several factory values and ranges; where it does, this page says so. Get the documents from danfoss.com and check them against your drive's firmware. The “our reading” notes are ours, not Danfoss statements. Danfoss and VLT are trademarks of Danfoss A/S; BACManager is not affiliated with Danfoss. The pictures on this page are from BACManager connected to a simulated drive built from the published object table.

// more device guides

Other BACnet devices

Chillers and rooftop units
Daikin MicroTech III chiller
Trane Symbio 700
Carrier AquaSnap 30RC
York YLAA chiller
AAON VCCX2
Lennox CORE
Air handling units
Swegon GOLD
Systemair Access (Geniox, Topvex)
VAV and room controllers
KMC Conquest VAV
Data centre cooling
Vertiv Liebert iCOM
Boilers
Lochinvar Crest boiler
VRF and split systems
Daikin iTM (VRV)
Mitsubishi AE-200
Drives
ABB ACH580
Schneider ATV600
Siemens SINAMICS G120P
Yaskawa HV600
Pumps and valves
Grundfos MAGNA3 (CIM)
Wilo Stratos MAXO (CIF)
Belimo Energy Valve
Energy meters
Accuenergy Acuvim II
Routers
BASrouter (MS/TP to IP)

All BACnet device guides →

Commission the FC 102 from your laptop

Download the free trial, discover the drive and open the FC 102 workspace — every point by name, the reference re-written for the control timeout. No credit card.

Download free trial See pricing

Windows 10/11 · $149 one-time