How to bring a Swegon GOLD air handling unit onto a BMS through the BACnet/IP that is built into its IQlogic control: the External Port B address every unit leaves the factory with (10.200.1.1), the Device ID that is 0 on every unit, the one object that starts, stops and switches speed (MV 793), the points a BMS uses — and which generation the published object list belongs to. With a free BACManager workspace.
Sources: Swegon BACnet IP GOLD RX/PX/CX/SD, Generation E (GOLD_E_BACnet_150316, 2015-03-16), Swegon GOLD BACnet PICS Version E (2014-04-29) and the GOLD version F/G function manual GB.GOLDSKFFI.20260610 (program 2.47)
GOLD RX, PX, CX and SD units speak BACnet/IP on the control unit's Ethernet port, which the menus call External Port B. The PICS lists BACnet/IP as the only data link: there is no BACnet MS/TP. The unit's EIA-485 port offers Modbus (factory), EXOline, Metasys N2 Open or LON instead. Swegon's “BACnet gateway” documents are for other products, not GOLD.
GOLD has been sold as version E (2013–2017), F (from 2017) and now F/G. Swegon's published BACnet object list is for Generation E, program version 1.10 and newer. We found no public object list or EDE file for F or G. The points below are from the Generation E list; on a newer unit, read the unit's own object list and compare, or ask Swegon for the EDE file of your program version.
Swegon calls GOLD a B-AAC. ReadProperty(Multiple), WriteProperty(Multiple), COV, alarm and event notifications with acknowledge and GetEventInformation, an internal schedule, time synchronisation and reinitialize. Segmented requests and responses, window 32. Vendor ID 300, protocol revision 12. Max APDU and a BTL listing: not given in the documents we found.
On the IQnavigator hand-held terminal or the unit's web page, under Communication. Factory settings as the F/G function manual (program 2.47) lists them.
| Setting | Factory | Set to |
|---|---|---|
| External Port B → DHCP | Off | Usually off: a BMS wants a fixed address |
| External Port B → IP address | 10.200.1.1 | A free address in the BMS network. Every unit leaves the factory with this one |
| Net mask / Default GATEWAY | 255.255.255.0 / 0.0.0.0 | The BMS network's mask; a gateway when the BMS is in another subnet |
| BACnet IP → Device ID | 0 | A device instance unique in the building |
| BACnet IP → Port number | 47808 | Leave, unless the site uses another UDP port |
| BACnet IP → Network number Ext. B / Internal network number A | 0 / 0 | Listed without an explanation in the manual; leave unless your BACnet network plan gives numbers |
| Operation level communication | Inactive | The same choices as MV 793, with Inactive in place of Auto; whether it is the same setting is not stated — see below |
| Time and date → Time source | — | Manual, SNTP or BACnet |
The manual has no separate on/off switch for BACnet/IP, and does not say whether a changed address needs a restart — check the address answers before you leave the unit. Base setting saves and loads both the unit's settings and its communication settings (internal memory, SD card or USB stick). On units with program 2.47 delivered after August 2025 the local and installation logins of the web page are off by default; the service password is on a label on the control board and differs for every unit.
Communication operation level is a commandable multi-state value. Operation level (MI 592) reads back what the unit actually does and why.
| MV 793 state | Meaning | MI 592 then reads |
|---|---|---|
| 1 Auto | Default. The BMS does not command the speed | Whatever the timer or another source decides, e.g. 24 Time channel low speed |
| 2 Total stop | Stopped; no internal automatic function or external command can start it | 5 Communication total stop |
| 3 Low speed | Runs at the low speed set points | 23 Communication low speed |
| 4 High speed | Runs at the high speed set points | 30 Communication high speed |
| 5 Normal stop | Stopped, but internal and external automatic functions may start it | 6 Communication normal stop |
| 6 Extended normal stop | As normal stop, except summer night cooling | 7 Communication extended normal stop |
The Generation E list calls state 1 “Auto”; the F/G terminal menu calls the factory setting “Inactive”. Neither document says in words what it hands control back to. We read it as “communication does not decide”; watch MI 592 after writing it.
The analog, binary and multi-state values carry a priority array and a relinquish default, but Swegon gives no recommended priority. BACManager writes at priority 8 unless you choose otherwise. A value written stays until it is relinquished — see the priority array explained.
The low speed air flow set point (AV 3) can go no higher than the high speed one (AV 5), which can go no higher than the max speed one (AV 7). Raise high speed first. Supply air temperature set point AV 132: 10–40 °C, default 21, used in SA regulation mode (MV 115 = 4).
Two GOLD units on one network answer Who-Is with the same device instance until someone sets it. Give each unit its own Device ID before the BMS discovers them.
External Port B is static 10.200.1.1/24 from the factory. A second new unit on the same switch is an address conflict, and a BMS in another subnet will not find either one. Set the address first.
Written from the BMS, Total stop also keeps the unit's own automatic functions from starting it. Use Normal stop when night heating or cooling should still run, and remember a value at priority 8 outlives the BMS that wrote it.
From Swegon's Generation E list (program version 1.10 and newer), object names as Swegon writes them. C = commandable (priority array), R = read only. On F or G units, check each one against the unit's object list.
| Object | Object name | Access | What it is |
|---|---|---|---|
| MV 793 | Communication operation level | C | 1 Auto, 2 Total stop, 3 Low speed, 4 High speed, 5 Normal stop, 6 Extended normal stop |
| MI 592 | Operation level | R | What the unit runs at and why, 41 states (manual, external, communication, time channel…) |
| BI 1 / 2 / 3 / 4 | Operation active / Damper operation active / Low speed operation active / High speed operation active | R | Run and speed status |
| BI 13 / BI 14 | A-alarm active / B-alarm active | R | Any alarm of priority class A / B |
| AI 604–613 | Triggered alarm #1…#10 | R | (group − 1) × 15 + number in group; 0 = none |
| BV 1 | Alarm reset | C | Resets all active alarms |
| AI 64 / 66 / 68 | SA Temperature / EA Temperature / EA Regulation temperature | R | °C, −55…125 |
| AI 73 / 74 | Outdoor temperature / Outdoor regulation temperature | R | °C |
| AV 132 | SA temperature set point | C | 10–40 °C, default 21 (SA regulation mode) |
| AV 135 / 136 / 137 | EA/Room temperature set point / SA min temp set point / SA max temp set point | C | EA/room regulation: default 21, 16, 28 °C |
| MV 115 | Temperature regulation mode | C | 1 Inactive, 2 ERS-1, 3 ERS-2, 4 SA (default), 5 EA, 6 ORS, 7 ORE |
| AI 4 / AI 6 | SA Air flow / EA Air flow | R | l/s |
| AV 3 / 4, AV 5 / 6 | SA / EA low speed air flow set point, SA / EA high speed air flow set point | C | l/s; low ≤ high ≤ max (AV 7 / 8) |
| AI 8 / 10, AV 19–22 | SA / EA Duct pressure, low / high speed pressure set points | R / C | Pa, for pressure regulation |
| MV 1 / MV 2 | SA / EA Fan regulation mode | C | 1 Air flow reg., 2 Pressure reg., 3 Demand reg., 4 Slave controlled |
| AI 37–46 | SA / EA Fan level, Fan speed, Voltage, Fan current, Fan power | R | %, rpm, V, A, kW |
| AI 47 / 48 + AI 49 / 50 | SA / EA Fan kWh + SA / EA Fan MWh | R | kWh counts 0–9999; read MWh with it |
| AI 63 | SFP | R | Specific fan power, kW/(m³/s) |
| AI 27 / 28, AI 29 / 30 | SA / EA AHU filter pressure level / alarm limit | R | Pa; settings AV 103 / 104, 30–500, default 100 |
| AI 91 / 94 / 101 | Heat exchanger regulator level / Reheat regulator level / Cool regulator level | R | Heat recovery, reheat and cooling, % |
| AI 105 / 106 | RHX operation level / RHX efficiency | R | Rotary heat exchanger, % |
| BI 38 / 43 / 44 | Re-heat output / Cool output 1 / Cool output 2 | R | Relay outputs |
| BI 501… | Alarm group:number | R | One object per alarm, e.g. BI 892 Alarm 27:2, AHU filter supply air dirty |
| Schedule 0, Calendar 0 / 1 | Schedule #1, Calendar #1 / #2 | C | Values 1 Total stop, 2 Low, 3 High, 4 Normal stop, 5 Extended normal stop; 6 times a day, 2 exceptions; 10 dates per calendar |
| Notification Class 0 / 1 / 3 / 10 / 11 | NC 00 A-Alarm, NC 01 B-Alarm… | — | A-alarm, B-alarm, alarms in BACnet objects, info message, events |
The full Generation E list runs to 60 pages: pre-filters and end filters, pre-heat, extra regulation sequences, Xzone, ReCO2, humidity, COOL DX, SMART Link and MIRU zone controls. Much of it concerns optional functions. BACManager reads the schedule and calendars into its editor, and can receive the unit's alarm notifications and acknowledge them; the PC must be a recipient in the notification class for that.
One dashboard page for a GOLD with heat wheel, reheat and cooling: the unit with outdoor and supply air, air flow, cooling and reheat levels; both fans with flow, level and current; operation level, A- and B-alarm; and the BMS commands at priority 8.
On the BACnet tab open BACnet/IP on the PC's network card in the unit's subnet and press Discover. From another subnet, register with the site's BBMD as a foreign device. The unit appears with its Device ID.
Workspace → Open. The file reads device 20101; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.
On the Dashboard press Run. The commands write at priority 8 only in Run mode and only after the unit has answered. Set MV 793 back to Auto to hand the unit back to its own timer.
| What you see | Why | What to do |
|---|---|---|
| Discover finds nothing | External Port B still on 10.200.1.1/24, the BMS in another subnet | Set the unit's address, mask and gateway; across routers use a BBMD |
| Two units answer as instance 0 | Device ID factory value | Set the Device ID on every unit |
| Address conflict when the second unit is connected | Both are 10.200.1.1 | Address each unit before it goes on the shared network |
| Unit will not start, from the BMS or its timer | MV 793 left at Total stop, or a stop from the terminal or a digital input | Read MI 592: 3 manual, 4 external, 5 communication, 8 time channel total stop |
| Low speed air flow will not go higher | AV 3 is limited by the high speed set point AV 5 | Raise AV 5 first (and AV 7 above it if needed) |
| An object from this list is missing | Function not configured, or an F/G unit whose list differs | Read the unit's object list by name; ask Swegon for the EDE of your program version |
| Fan energy drops back to a small number | The kWh object counts only to 9999 | Read the MWh object with it |
| Web page login refused on a new unit | Program 2.47, delivered after August 2025: local and installation logins off | Use the service password from the label on the control board |
Swegon AB: BACnet IP GOLD RX/PX/CX/SD, Generation E — applicable to program version 1.10 and newer versions, GOLD_E_BACnet_150316 (16 March 2015); Swegon GOLD BACnet PICS Version E, 29 April 2014 (application software 1.11); and GOLD Air Handling Unit, Function manual, installation, GOLD RX/PX/CX/SD version F/G, program version 2.47 and newer, GB.GOLDSKFFI.20260610. Get the documents from swegon.com and check them against your unit's program version. The points list is Generation E; for F and G units no public object list was found. What MV 793 “Auto” hands back to is our reading, not a Swegon statement. Swegon, GOLD and IQlogic are trademarks of Swegon AB; BACManager is not affiliated with Swegon. The pictures on this page are from BACManager connected to a simulated unit built from the published Generation E object list.
Download the free trial, discover the unit and open the GOLD workspace — every point by name, start, stop and speed at priority 8. No credit card.
Windows 10/11 · $149 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off.