How to bring a KMC Conquest BAC-9001A VAV controller-actuator onto a BMS over BACnet MS/TP or BACnet/IP: the NetSensor COMM menu, the Restore menu that wipes your setpoints when you change the units, the factory object list of the single-duct VAV application in °F and cfm — and why a BMS should write the occupied setpoints, not the active ones that KMC's own program keeps recalculating. With a free BACManager workspace.
Source: KMC Conquest Gen6 Controller Application Guide AG250415B and data sheet 925-035-02C (BAC-9000A series)
The BAC-9001A is the pressure-independent VAV controller-actuator (single or dual duct), the BAC-9021A the pressure-dependent one. The “A” suffix marks KMC's Gen6 hardware. The BAC-9300A series is the unitary controller, not covered here. Each model comes with an MS/TP port or, on “E” models such as the BAC-9001ACE, two Ethernet ports.
One EIA-485 port, 9.6 to 115.2 kbaud, up to 1200 m of 18 AWG shielded twisted pair. Turn the EOL switch on only in the two end controllers (they ship off). KMC allows 128 masters per network but recommends about 30 controllers; beyond 31 devices or 1220 m use a repeater or a router. More in BACnet MS/TP over RS-485.
B-AAC: ReadProperty, ReadPropertyMultiple, WriteProperty and WritePropertyMultiple, COV, alarms and events, schedules, trend logs, segmentation (window 7). That is from KMC's 2017 PICS and BTL listing BTL-30013, which cover the earlier Gen5 models; the Gen6 data sheet says BTL-certified as a B-AAC.
| Setting | Where | What KMC gives |
|---|---|---|
| Device instance | NetSensor: Configuration → COMM → D ID | Factory value not given in the guide or data sheet — read it from the controller and make it unique |
| MS/TP MAC | COMM → MAC | Factory value not given |
| Baud rate | COMM → BAUD | 9.6, 19.2, 38.4, 57.6, 76.8 or 115.2 k; the same on every controller of the trunk. Factory value not given |
| Max Master | A configuration tool only (KMC Connect, TotalControl, Converge) | “Just” above the highest MAC on the trunk |
| IP address (“E” models) | KMC Connect, TotalControl, Converge or the controller's web pages — not the NetSensor | 192.168.1.251, mask 255.255.255.0, gateway 192.168.1.1. BACnet/IP, Foreign Device or Ethernet 802.3 |
| Application and units | NetSensor: Configuration → RSTR | Single or dual duct VAV …; English, Metric or mixed units |
The NetSensor's configuration menus open with the Up and Down buttons held together for six seconds and the level 2 password; KMC hands out the default password in a technical bulletin for logged-in users. The same settings can be made with the KMC Connect Lite app over NFC while the controller is unpowered. Never plug the Ethernet cable into the Room Sensor jack: it powers the NetSensor and can damage a switch. Across IP subnets you need a BBMD or foreign-device registration — see BBMD and foreign devices.
KMC's factory programs decide the setpoint in force from the occupancy. A BMS that writes the wrong object sees its value replaced.
| State | Active cooling AV3 | Active heating AV4 | What a BMS writes |
|---|---|---|---|
| Occupied | = AV5 OCC CL STPT (74) | = AV6 OCC HT STPT (70) | AV5 / AV6 to move the comfort setpoints |
| Standby | AV5 + AV12 STBY_OFFSET (3) | AV6 − AV12 | AV12 for a wider standby band |
| Unoccupied | = AV7 UNOCC CL STPT (80) | = AV8 UNOCC HT STPT (64) | AV7 / AV8 for night setback |
The guide says the controller places AV5–AV8 into AV3/AV4 whenever the occupancy changes, and that a setpoint entered at the NetSensor (through AV3/AV4) lasts only for a limited time or until the next occupancy change. So treat AV3/AV4 as read-only from the BMS. Values in °F are the factory defaults in English units.
AV11 MIN STPT DIFF (4 °F) keeps heating below cooling. KMC's example: with heating at 70, lowering the occupied cooling setpoint to 71 makes the controller move occupied heating to 67. Write cooling and heating as a pair and read both back.
KMC's PICS gives the value objects a priority array and relinquish default, but no document we found says which priority a BMS should use. BACManager writes at priority 8 unless you choose another. A cold start returns every present value to its relinquish default.
Occupancy normally comes from the controller's own BACnet Schedule object, which a BMS can edit like any other — see the schedule editor. KMC also says occupancy “can be commanded” by another BACnet device, without naming the object; MSV1 OCCUPIED MODE is the obvious candidate, and the free workspace writes it, but try it on your controller first.
The factory objects are in °F and cfm. Switching to Metric — or changing the application — in RSTR restores the Setpoint, System and Balance menus to factory defaults (communication settings and passwords stay). Choose application and units first, let the controller restart for at least 30 s, then commission.
Airflow is calculated from the box's differential pressure and the K factor in AV18 PRI K FACT (904 from the factory). With the wrong K factor every cfm reading is wrong. KMC's guide lists K factors per box in an appendix; balancing with a flow hood then sets the correction factors.
The objects depend on the model and the application chosen in RSTR, and can be created and deleted with KMC's tools. Read the device's object list instead of assuming a table, and don't reuse KMC's default objects for custom programs: a firmware upgrade can overwrite them.
BAC-9001A, pressure independent, single duct, English units. Object names and factory defaults as KMC's table lists them; the table has no access column.
| Object | Object name | Default | What it is |
|---|---|---|---|
| AV1 | SPACE TEMP | — | Space temperature the loops use, °F (from the NetSensor or AI1) |
| AV3 / AV4 | ACT COOL STPT / ACT HEAT STPT | 74 / 70 | Setpoints in force, recalculated by the program |
| AV5 / AV6 | OCC CL STPT / OCC HT STPT | 74 / 70 | Occupied setpoints |
| AV7 / AV8 | UNOCC CL STPT / UNOCC HT STPT | 80 / 64 | Unoccupied setpoints |
| AV9 / AV10 / AV11 | MIN CL STPT / MAX HT STPT / MIN STPT DIFF | 68 / 76 / 4 | Setpoint limits and the minimum heating–cooling gap |
| AV2 / AV12 | STPT REFERENCE / STBY_OFFSET | 72 / 3 | Setpoint reference; standby offset (also the range of an STE-6014/6017 dial) |
| AV13 / AV14 | MIN COOL FLOW / MAX COOL FLOW | 100 / 400 | Cooling airflow range, cfm |
| AV15 / AV16 / AV17 | MIN HEAT FLOW / MAX HEAT FLOW / AUXILLARY FLOW | 100 / 400 / 200 | Heating airflow range; airflow during reheat (KMC's spelling) |
| AV22 / AV23 / AV24 | PRI FLOW STPT / PRI RAW FLOW / PRI ACTUAL FLOW | — | Airflow setpoint, uncorrected and corrected airflow, cfm |
| AV18–AV21 | PRI K FACT, PRI CORR SLOPE, PRI CORR OFFST, PRI LO FLOW CORR | 904, 1, 0, 1 | K factor and balancing corrections |
| AV50 | DAMPER POSITION | — | Damper position, % |
| AV36 / AV47 / AV37 | DAT RESET / DAT MAXIMUM / SAT CHANGEOVER | 90 / 90 / 72 | Discharge air setpoint and limit; supply air changeover temperature, °F |
| AV41 / AV57 | REL_HUMIDITY / ROOM CO2 | — | From NetSensors that have the sensor, % RH and ppm |
| AI3 | DISCHARGE AIR | — | Discharge air temperature (optional sensor, needed for heating and changeover) |
| AI1 / AI2 | SPACE SENSOR / SPACE SETPOINT | — | Only for analog STE-6010/6014/6017 sensors; unused with a NetSensor |
| AO3 / AO4 | ANALOG HEAT / FAN SPEED | 0 / 0 | Modulating reheat and fan speed outputs, % |
| BO1 / BO2, BO6, BO7–BO9 | PRI DAMPER CW / CCW, FAN, HT STAGE 1–3 | Inactive | Actuator drive, fan, heating stages |
| BV1 / BV2 / BV3 / BV7 | NEED AHU / NEED COLDER SPLY / NEED MORE STATIC / NEED HOTTER SPLY | Inactive | Requests to the air handler (below) |
| BV4 / BV5 / BV6 | LOCAL OVRD / MOTION OVRD / MOTION SENSOR | Inactive | Override and motion states |
| BV11 / BV12 | AUTO OCCUPANCY / BALANCE MODE | Inactive | Automatic occupancy enabled; balancing running |
| MSV1 | OCCUPIED MODE | OCCUPIED | 1 Occupied, 2 Standby, 3 Unoccupied, 4 Local override, 5 Motion override |
| MSV8 | OCCUPIED STATE | OCCUPIED | 1 Occupied, 2 Standby, 3 Unoccupied, 4 Local override |
| MSV2 / MSV3 / MSV10 | FAN CONFIG / REHEAT / WALL SENSOR | NONE / NONE / STE-9001 | Box configuration: fan type, reheat type, sensor type |
The four AHU flags, as the guide defines them: NEED AHU is on when the box is occupied or in standby, or unoccupied with a loop at 100 %, and off when both loops fall below 5 %. NEED COLDER SPLY and NEED HOTTER SPLY come on with the damper fully open and the cooling (or heating) loop above 95 % for 30 minutes, and go off below 90 %. NEED MORE STATIC means the damper is fully open and the airflow still cannot reach its setpoint. The dual-duct application adds secondary duct objects, and the BAC-9021A pressure-dependent application has its own table.
One dashboard page for a single-duct VAV box: the room faceplate with space temperature, the occupied setpoints and occupancy, the damper, airflow against its setpoint, discharge air, reheat, the active setpoints, the AHU flags, the writable airflow range and two trends.
On the BACnet tab open BACnet/IP for an “E” model, or MS/TP on the PC's RS-485 port at the trunk's baud rate (or through a router), and press Discover. The controller appears with the instance set in D ID.
Workspace → Open. The file reads device 30214; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.
On the Dashboard press Run. The faceplate's + and − write the occupied setpoints AV5/AV6 at priority 8; the active setpoints next to the damper show what the program made of them. If the controller was restored to Metric, change the unit labels on the elements and the trend ranges to match.
| What you see | Why | What to do |
|---|---|---|
| A setpoint written to AV3/AV4 springs back | The program places AV5–AV8 into the active setpoints on every occupancy change | Write AV5/AV6 (occupied) or AV7/AV8 (unoccupied) |
| Heating setpoint moved by itself | AV11 minimum differential: the controller keeps heating 4 °F below cooling | Write the pair; read both back |
| All setpoints and airflows back at factory values | Application or units changed in RSTR | Choose application and units first, then commission |
| Values look like °F although the site is metric | The controller is still in English units | RSTR → Metric before commissioning (it restores defaults) |
| Airflow readings wrong by a constant factor | Wrong K factor in AV18, or the box not balanced | Enter the box's K factor and balance with a flow hood |
| Box stops answering BMS changes for a while | Balancing (BLNC) running: it locks out all other functions | Wait for BV12 BALANCE MODE to clear |
| Controllers at high MACs missing on MS/TP | Max Master below the highest MAC, or mixed baud rates | Max Master just above the highest MAC; one baud rate per trunk |
| Box goes Unoccupied and the damper opens fully | Automatic occupancy enabled and primary airflow lost (under 25 % of the request for 5 minutes) | Check the air handler; automatic occupancy is off from the factory |
| AI1 / AI2 read nothing | A digital NetSensor is fitted; they serve analog sensors only | Read AV1 for the space temperature |
KMC Controls: KMC Conquest Gen6 Controller Application Guide AG250415B (2025; MS/TP and Ethernet connections, NetSensor menus, VAV sequences, BAC-9001A object tables), data sheet BAC-9000A Series BACnet VAV Controller-Actuators 925-035-02C (2024), and the PICS KMC Conquest Controllers Combined Rev B and BTL listing BTL-30013 (both February 2017, firmware R1.1.0.0). Get the documents from kmccontrols.com and check them against your controller's firmware and application. Where the guide disagrees with itself we followed the object table: two passages map the NetSensor setpoints to AV4/AV5 while the table, the sequences and a third passage use AV3/AV4, and the text gives a 74 °F changeover default where AV37 lists 72. The factory device instance, MAC, baud rate and a recommended write priority are not in these documents; the occupancy object is our reading. KMC Conquest is a trademark of KMC Controls, Inc.; BACManager is not affiliated with KMC Controls. The pictures on this page are from BACManager connected to a simulated controller built from the published object table.
Download the free trial, discover the box and open the Conquest VAV workspace — every point by name, the occupied setpoints on the room faceplate. No credit card.
Windows 10/11 · $149 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off.