How to put a Carrier AquaSnap 30RC air-cooled chiller with the Carrier Controller on BACnet/IP: the BACNET menu that is off from the factory, the Ethernet port and its 169.254.1.1 default, the device ID 1600001, the Network control method without which every command is ignored — and the metric units BACnet uses even when the display shows °F. With a free BACManager workspace.
Covers 30RC 010–060, also with Greenspeed Intelligence · source: Carrier Form 30RC-100T, Catalog No. 04-53300249-01 (3-24)
The Carrier Controller display is the chiller's controller and its BMS interface. Its RJ45 port J5 (ETH0) carries BACnet, Modbus TCP and the web interface. The BACNET menu offers BACnet/IP or BACnet MS/TP; the form does not say which terminal MS/TP uses on this chiller.
The BACNET menu's bacena is 0 (disabled), and the factory configuration has bac_opt “Enable BacNet Option” = No. The form lists both without saying how they relate; the factory menu needs the Factory access level. If BACnet stays silent, ask Carrier service to check bac_opt.
On the display's Start/Stop screen pick Network. In Local On, Local Schedule or Remote the chiller reads fine but ignores every network command except Emergency Stop. Start/stop from the web interface is not allowed at all, for security.
The IP address of Ethernet 0 (J5) is set under System Menu → Network; its default is 169.254.1.1. BACnet itself is under Main Menu → Configuration → BACNET (User access).
| Point | Setting | Factory | Set to |
|---|---|---|---|
| bacena | BACnet Enable Option | 0 Disabled | 1 BACnet IP (or 2 BACnet MS/TP) |
| bac_id | Device ID Manual | 1600001 | A device instance unique in the building (1–4194302) |
| auid_opt | Device ID Auto Option | Disabled | Leave, unless your site uses the automatic scheme |
| network | Network | 1600 | 1–40000; leave unless your BACnet network plan gives a number |
| udpport | UDP Port Number | 47808 | 47808–47823 |
| bacunit | Metric Units? | Yes | Yes = °C and kPa over BACnet; No = °F and psi |
| balmena | Alarm Reporting | Enabled | Leave |
| mng_occ | BACnet Manage Occupancy | No | Yes when the BMS sends occupancy through BACnet_BMS_OCC (AV 66) |
| conifnam | IP Port Interface Name | 0 = J5 / J15 | 1 = J16 |
| mstpaddr / mstpbaud | MS/TP MAC / baud | 1 / 2 = 38400 | MS/TP only: a free MAC 1–127; 9600…115200 |
| maxmastr / maxinfof | Max Master / Max Info Frames | 10 / 5 | MS/TP only: Max Master = the trunk's highest MAC |
Two read-only objects tell you what the controller really uses: BACnet_ident (AV 63) “Device Id Actually Used” and BACnet_bacunit (BV 61). The display's own units are separate and default to US Imperial, so the screen can show 44.6 °F while BACnet reads 7.0 °C.
Each network command exists twice: an RW object ending in _wr at 10000 + the instance of the read-only _rd object that shows the value in force.
| Write | Object name | Read back | What it does |
|---|---|---|---|
| BV 10012 | GENUNIT_CHIL_S_S_wr | BV 12 | Net.: Cmd Start/Stop, 1 = enable |
| BV 10058 | GENUNIT_CHIL_OCC_wr | BV 58 | Net.: Cmd Occupied |
| AV 10006 | GENUNIT_CTRL_PNT_wr | AV 6 | Control point, −4…153 °F in the table (−20…67 °C) |
| AV 10008 | GENUNIT_DEM_LIM_wr | AV 8 | Demand limit, 0–100 % |
| AV 10024 | GENUNIT_SP_SEL_wr | AV 24 | Setpoint select: 0 Auto, 1 Setpoint 1, 2 Setpoint 2 |
| AV 10023 | GENUNIT_HC_SEL_wr | AV 23 | Heat/cool select: 0 Cool, 1 Heat, 2 Auto |
| BV 10013 | GENUNIT_EMSTOP_wr | BV 13 | Emergency Stop — acts in every control method |
| BV 10050 / 10051 / 10053 | PUMPSTAT_PUMP_1_wr / _2_wr, PROTOCOL_PUMP_C | BV 50 / 51 | Evaporator pumps, condenser pump |
Carrier's start/stop table lists the Network method as running only with Start/Stop enabled and the time schedule occupied. If BV 12 reads 1 and the chiller still stays off, check BV 58 — and write BV 10058 = 1, or occupancy through AV 66 with mng_occ = Yes.
The chiller controls to the control point: the current setpoint plus any reset. SETPOINT_csp1 (AV 900, default 44.6 °F = 7.0 °C) is a plain read-write setting; GENUNIT_CTRL_PNT_wr forces the control point directly while Network is active.
The form marks the _wr objects RW but does not say whether they carry a priority array or which priority a BMS should use. BACManager writes at priority 8 unless you choose otherwise; a commanded value stays until it is relinquished — see the priority array explained.
Local On, Local Schedule and Remote ignore BACnet start/stop, setpoint and demand limit writes. Read GENUNIT_CTRL_TYP (AV 21: 0 Local, 1 Network, 2 Remote) before blaming the BMS. Changing the method passes through Off, with the on-to-off delay.
The manual device ID is 1600001 on every controller. Two 30RCs on one network answer Who-Is with the same instance until bac_id is changed on one of them (or the automatic scheme is set up).
Metric Units? = Yes from the factory: BACnet reads °C and kPa while the display and the form's point tables give °F and PSI. A BMS that expects °F reads 7 as freezing. Pick one and label the points.
Object names as Carrier lists them in Form 30RC-100T Appendix D. RW = written by the BMS, R = read only. Which points answer depends on the unit's options; circuit B and the third compressor exist only where fitted.
| Object | Object name | Access | What it is |
|---|---|---|---|
| AV 1 / AV 2 | TEMP_EWT / TEMP_LWT | R | Entering and leaving water |
| AV 3 | TEMP_OAT | R | Outdoor air |
| AV 6 / AV 7 | GENUNIT_CTRL_PNT_rd / GENUNIT_SP | R | Control point in force; current setpoint |
| AV 9 | GENUNIT_CAP_T | R | Percent total capacity |
| AV 1017 / AV 2017 | GENUNIT_CAPA_T / GENUNIT_CAPB_T | R | Circuit A / B capacity, % |
| AV 21 | GENUNIT_CTRL_TYP | R | 0 Local, 1 Network, 2 Remote |
| AV 22 | GENUNIT_STATUS | R | Running status (Off, Delay, Running, Ready, Tripout…; the numbers are not listed) |
| AV 11 | GENUNIT_min_left | R | Minutes left for start |
| BV 15 / BV 16 | OUTPUTS_RUN / INPUTS_ONOFF_SW | R | Running relay; remote on/off contact |
| BV 50 / 51 / 52 | PUMPSTAT_PUMP_1_rd / _2_rd, INPUTS_FLOW_SW | R | Water pumps; flow switch interlock |
| AV 900 / 901 | SETPOINT_csp1 / SETPOINT_csp2 | RW | Cooling setpoints 1 and 2, −20…68 °F in the table |
| AV 903 / 904 | SETPOINT_hsp1 / SETPOINT_hsp2 | RW | Heating setpoints |
| AV 905–907 | SETPOINT_lim_sp1…3 | RW | Switch limit setpoints, % |
| AV 66 | BACnet_BMS_OCC | RW | BMS occupancy: 0 unoccupied, 1 occupied, 2 none (with mng_occ = Yes) |
| BV 1032, 1033, 1034 / 2032, 2033 | OUTPUTS_CP_A1, A2, A3 / B1, B2 | R | Compressors running |
| AV 1000 / 1001, AV 2000 / 2001 | PRESSURE_DP_A / SP_A, DP_B / SP_B | R | Discharge and suction pressure |
| AV 1005 / 1006, AV 2005 / 2006 | TEMP_SCT_A / SST_A, SCT_B / SST_B | R | Saturated condensing and suction temperatures |
| AV 1009 / 2009, AV 1011 / 2011 | TEMP_DGT_A / B, LOADFACT_SH_A / B | R | Discharge gas temperature; suction superheat |
| AV 1015 | OUTPUTS_VFAN | R | VariaFan speed |
| AV 960 / 961 | RUNTIME_hr_mach / RUNTIME_st_mach | R | Machine hours and starts; per compressor AV 1960… / 1964… |
| AV 980–984 / 985–989 | ALARMRST_alarm_1c…5c / alarm_1…5 | R | Current alarms 1–5 (code, e.g. 10031) and their index |
| AV 990 / BV 5012 | ALARMRST_ALM / OUTPUTS_ALARM | R | Alarm state; alarm relay |
| BV 1xxxxx | ALM_…_F | R | One object per alarm, e.g. BV 115002 ALM_COOL_LWT_F, BV 110001 ALM_COOLER_FREEZE_F |
| AV 62 / AV 63 / BV 61 | BACnet_network / BACnet_ident / BACnet_bacunit | R | The BACnet settings in force |
The full table, with every alarm object, the pump configuration and the model-specific 5000-range points, is Appendix D of Form 30RC-100T (pages 142–147); Appendix E gives the same data as Modbus TCP registers. The table's limits are written in °F; over BACnet with Metric Units? = Yes the values arrive in °C. With Alarm Reporting enabled, BACManager can receive the alarm notifications the chiller sends; the form does not describe its alarm services or how the recipients are set.
One dashboard page for the chiller: the unit with compressors A1, A2, B1, B2, leaving and entering water and capacity; control type, running and alarm relay; circuit A refrigerant values; and the network commands at priority 8 — start/stop, occupied, control point, demand limit, emergency stop and cooling setpoint 1.
On the BACnet tab open BACnet/IP on the PC's network card and press Discover — from another subnet through the site's BBMD as a foreign device, or MS/TP on a USB RS-485 adapter if the chiller is set to MS/TP.
Workspace → Open. The file reads device 1600001, the factory bac_id; if yours has another instance, BACManager asks which discovered device takes its place and moves every point over.
Check the control type reads Network. On the Dashboard press Run: the commands write only in Run mode and only after the chiller has answered.
| What you see | Why | What to do |
|---|---|---|
| Discover finds nothing | bacena still 0, bac_opt No, or J5 on 169.254.1.1 | Set the IP address, then bacena = 1; have Carrier service check bac_opt |
| Writes succeed, nothing changes | Machine Control Method is Local or Remote | Select Network on the display; read AV 21 = 1 |
| Start/Stop enabled, chiller stays off | Network also needs the schedule occupied | Write BV 10058 = 1, or occupancy via AV 66 with mng_occ = Yes |
| Temperatures look wrong by a lot | BACnet in metric, the BMS expects °F (or the reverse) | Check BV 61 and bacunit; label the points |
| Two chillers answer as 1600001 | bac_id factory value | Set a unique Device ID on each |
| Chiller stopped, Current Alarm 1 = 10031 | Emergency Stop written over the network | Write BV 10013 = 0 (it resets automatically) |
| On MS/TP the chiller ignores masters above MAC 10 | Max Master factory value 10 | maxmastr = the trunk's highest MAC |
| A point from this list is missing | Option not fitted, or another software version | Read the object list from the chiller by name |
Carrier: AquaSnap 30RC 010–060 Air-Cooled Chillers (with Greenspeed Intelligence) and Carrier Controller — Controls, Start-Up, Operation, Service and Troubleshooting, Form 30RC-100T, Catalog No. 04-53300249-01, 3-24: the BACNET and Network menus (Appendix A and H), Machine Control Methods and Table 24, and Appendix D “BACnet IP points”. Get it from carrier.com and check it against your unit's software. Not in the form: the BACnet PICS, the priority to command at, the numbers behind GENUNIT_STATUS, and how bacena and bac_opt relate. Carrier and AquaSnap are trademarks of Carrier; BACManager is not affiliated with Carrier. The pictures on this page are from BACManager connected to a simulated controller built from the published BACnet table.
Download the free trial, discover the chiller and open the 30RC workspace — every point by name, start/stop and setpoints at priority 8. No credit card.
Windows 10/11 · $149 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off.